Technical data
4.5 Unit data
SINAMICS DCM DC Converter
Operating Instructions, 12/2018, A5E34763375A
51
Table 4- 13 Technical data for 3-ph. 480 V AC, 210 A to 280 A, 2Q devices
Article number 6RA80 ..
..75-6FS22-...
..78-6FS22-...
Rated DC current
A
210
280
Rated armature input current
2)
A
174
232
Rated power
kW
121
161
Power loss at
rated DC current (approx.)
W
720
811
Rated field DC current
A
15
15
Type of cooling
Forced ventilation
Forced ventilation
Rated fan supply voltage
V
Fan with internal power supply
Fan with internal power supply
Fan air flow
m
3
/h
300
300
Fan noise level
dB(A)
70.3
70.3
Dimensions (WxHxD)
mm
268x385x252
268x385x252
Weight (approx.)
kg
14
15
Table 4- 14 Technical data for 3-ph. 480 V AC, 450 A to 1200 A, 2Q devices
Article number 6RA80 ..
..82-6FS22-...
..85-6FS22-...
..87-6FS22-...
..91-6FS22-...
Rated DC current
A
450
600
850
1200
Rated armature input current
2)
A
374
498
706
996
Rated power
kW
259
345
489
690
Power loss at
rated DC current (approx.)
W
1583
1909
2597
4237
Rated field DC current
A
25
25
30
40
Type of cooling
Forced
ventilation
Forced
ventilation
Forced
ventilation
Forced
ventilation
Rated fan supply voltage
50 Hz
V
3-ph. 400 V AC
(±15%)
3-ph. 400 V AC
(±15%)
3-ph. 400 V AC
(±15%)
3-ph. 400 V AC
(±10%)
60 Hz
V
3-ph. 460 V AC
(±10%)
3-ph. 460 V AC
(±10%)
3-ph. 460 V AC
(±10%)
3-ph. 460 V AC
(±10%)
V
With option L21: 1-ph. 230 V AC (±10%)
Rated fan current
50 Hz
60 Hz
A
0.27
0.33
0.27
0.33
0.27
0.33
0.38
0.5
Rated fan current
with option L21
50 Hz
60 Hz
A
0.68
0.95
0.68
0.95
0.68
0.95
1.16
1.7
Fan air flow
m
3
/h
600
600
600
1000
Fan noise level
50 Hz
60 Hz
dB(A)
70.3
74.4
70.3
74.4
70.3
74.4
70.4
74.2
Dimensions (WxHxD)
mm
268x625x275
268x625x275
268x700x311
268x785x435
Weight (approx.)
kg
28
28
38
78
Содержание SINAMICS Series
Страница 1: ......
Страница 2: ......
Страница 744: ...Appendix A A 4 Servicing SINAMICS DCM DC Converter 742 Operating Instructions 12 2018 A5E34763375A ...
Страница 758: ......