Descriptions of functions
10.6 Communication via SINAMICS Link
SINAMICS DCM DC Converter
520
Operating Instructions, 12/2018, A5E34763375A
10.6.4
Example
Task
Configure SINAMICS Link for two nodes and transfer the following values:
●
Send data from node 1 to node 2
–
r0898 CO/BO: Control word, sequence control, drive 1 (1 PZD), in the example PZD 1
–
r0079 CO: Total torque setpoint (2 PZD), in the example PZD 2
–
r0021 CO: Smoothed actual speed (2 PZD), in the example PZD 3
●
Send data from node 2 to node 1
–
r0899 CO/BO: Status word, sequence control, drive 2 (1 PZD), in the example PZD 1
●
IF1 is used for SINAMICS Link.
Procedure
1.
For all nodes, set p0009 = 1 to change the device configuration.
2.
For all CBE20 nodes, set the "SINAMICS Link" mode using p8835 = 3.
3.
Limit the maximum number of nodes for all nodes with p8811 = 8. By setting p8811,
parameter p8812[1] is preassigned, and parameter p8836, if necessary, is corrected.
4.
Assign the node numbers for the devices involved:
–
Node 1 (
≙
device 1): p8836 = 1
–
Node 2 (
≙
device 2): p8836 = 2
5.
Make the following interface setting for all nodes:
–
For IF1: p8839[0] = 2 (COMM BOARD)
–
For IF2: p8839[1] = 1 (Control Unit onboard)
6.
For both nodes p0009 = 0, carry out a "Copy RAM to ROM" followed by a POWER ON in
order to activate the modified firmware versions and the new settings in the CBE20.
7.
Define the send data for node 1:
–
Define the PZD that node 1 should send:
p2051[0] = drive1:r0898 (PZD 1)
p2061[1] = drive1:r0079 (PZD 2 + PZD 3)
p2061[3] = drive1:r0021 (PZD 4 + PZD 5)
–
Place these PZD in the send buffer (p8871) of node 1:
p8871[0] = 1 (r0898)
p8871[1] = 2 (r0079 1st part)
p8871[2] = 3 (r0079 2nd part)
p8871[3] = 4 (r0021 1st part)
p8871[4] = 5 (r0021 2nd part)