Commissioning
8.5 Commissioning with the STARTER commissioning tool
SINAMICS DCM DC Converter
304
Operating Instructions, 12/2018, A5E34763375A
Note
For 2Q devices, the rated DC voltage of the SINAMICS DCM specified in the technical data,
can only be achieved if the
α
G
limit (p50150) is set to 5°. The factory setting is 30°. In order
to reach the rated motor voltage (p50101[D]), the
α
G
limit must also be changed to 5°.
⇒
If you select speed-dependent current limiting, then in another setting form you can set the
required values (parameters p50104 ... p50109).
⇒
Click Next >
NOTICE
Ensure protection against overload
The data are very important for protecting against overload and must be entered correctly.