Operation
9.1 Basic information
SINAMICS DCM DC Converter
352
Operating Instructions, 12/2018, A5E34763375A
This data is saved in the non-volatile memory (ROM). All user data is deleted from the ROM
as follows:
p0009 = 30
Parameter reset
p0976 = 200
Start to delete all user data
The operation may take several minutes. The device automatically powers up during this
time. As a result, the device in STARTER goes offline. Re-connect with the drive. After this
has been done, p0976 is automatically set to 0 and p0009 is set to 0.
Note
Data on the memory card is not deleted by setting p0976 = 200. In spite of this, when
deleting all user data, it is not permissible that a memory card is inserted. An inserted
memory card would mean that for an automatic ramp-up after p0976 = 200, as usual, the
data would be read from the memory card (see also Chapter "Memory card functions").
The device would power-up with the parameter assignment from the memory card.
Access level
The parameters are subdivided into access levels. The SINAMICS DCM List Manual
specifies the access level at which the parameter can be displayed and modified. The
required access levels 0 to 4 can be set in p0003.
Table 9- 1
Access levels
Access level
Comment
0 User-defined
Parameter from the user-defined list (p0013)
1 Standard
Parameters for the simplest possible operations (e.g. p50303 = ramp-
function generator ramp-up time)
2 Extended
Parameters for handling the basic functions of the device
3 Expert
Expert knowledge is already required for these parameters (e.g. knowledge
of assigning BICO parameters).
4 Service
Please contact your local Siemens office for the password for parameters
with access level 4 (Service). It must be entered into p3950.