Descriptions of functions
10.12 Setpoint channel
SINAMICS DCM DC Converter
562
Operating Instructions, 12/2018, A5E34763375A
Ramp-function-generator tracking
The ramp-function generator output (r52190) is limited to the following values when ramp-
function generator tracking is active:
(-Mlimitx 1.25 / Kp + nact) < HLG output < (+Mlimit x 1.25 / Kp + nact)
When p50170 = 1 (closed-loop torque control), the following applies:
(-IA.limit x
Φ
Motor x 1.25 / Kp + nact) < HLG output < (+IA.limit x
Φ
Motor x 1.25 / Kp + nact)
When p50170 = 0 (closed-loop current control), the following applies:
(-IA.limit x 1.25 / Kp + nact) < HLG output < (+IA.limit x 1.25 / Kp + nact)
Φ
motor
Scaled motor flux (1 at rated excitation current)
nact
Actual speed value (r52167)
+Mlimit
Smallest positive torque limit (r52143)
-Mlimit
Smallest negative torque limit (r52144)
+IA.limit
Smallest positive current limit (r52131)
-IA.limit
Smallest negative current limit (r52132)
Kp
Active speed controller gain
If, however, the value added to nact would be less than 1%, then +1% or is -1% is added.
The "Ramp-function generator tracking" function prevents the ramp-function generator value
from straying too far from the actual speed value if the torque or current limit has been
reached.
Note
When ramp-function generator tracking is active, the filtering time of the speed setpoint
p50228 should be low (ideally = 0).
Limiting after ramp-function generator
This limiting stage can be used by freely selecting the input signal, independently from the
ramp-function generator.
A distinguishing feature of this type of limiting is that lower limiting can also be set to positive
values and upper limiting to negative values (see p50300 and p50301). In this case, a limit
set using this method acts as a lower limit (lower limiting value) for the output signal of the
ramp-function generator, with the sign inverted.
Example:
p50632.01 ... 04 = 1 (= 100.00%)
p50300 = 100.00 (%)
p50301 = 10.00 (%)
p50633.01-04 = 9 (= -100.00%)
results in the value range of r52170 being limited to b10.00% and +100.00%.