Descriptions of functions
10.21 Measuring the motor temperature
SINAMICS DCM DC Converter
Operating Instructions, 12/2018, A5E34763375A
587
10.21
Measuring the motor temperature
SINAMICS DCM provides the possibility of evaluating a temperature sensor integrated in the
motor (see the SINAMICS DCM Parameter Manual, function diagram 8030).
WARNING
Electric shock in the event of voltage flashovers at the temperature sensor
Voltage flashovers in the signal electronics can occur in motors without safe electrical
separation of the temperature sensors.
•
Use temperature sensors that comply with the specifications relating to safe electrical
separation.
The following measuring sensors can be evaluated.
●
KTY84
Approx. 350
Ω
up to approx. 2600
Ω
at -40 °C to +300 °C
Positive temperature coefficient, almost a linear characteristic
Figure 10-70 Characteristic KTY84
●
PTC thermistor acc. to DIN 44081 / 44082
600
Ω
, 1200
Ω
, 1330
Ω
or 2660
Ω
response temperature
Positive temperature coefficient, the resistance changes suddenly at the response
temperature
Note:
It is not possible to determine the actual temperature, it is only possible to identify as to
whether the response temperature has been exceeded or not.
●
PT100
Approx. 80
Ω
up to approx. 280
Ω
at -40 °C to +500 °C
Positive temperature coefficient, almost a linear characteristic