Maintenance
11.2 Replacing components
SINAMICS DCM DC Converter
Operating Instructions, 12/2018, A5E34763375A
695
Replacing fans in 1200 A devices
1.
Remove the front cover of the SINAMICS DC MASTER
2.
Withdraw the fan connector
①
and the fan monitoring
②
3.
Release the nuts
③
4.
Remove the fan including the fan support strut
5.
Install the new fan in the reverse sequence, tightening torque for the nuts
③
= 15 Nm
Figure 11-6 Replacing fans in 1200 A devices