Commissioning
8.3 Commissioning using the BOP20 operator panel
SINAMICS DCM DC Converter
278
Operating Instructions, 12/2018, A5E34763375A
〈
5.5
〉
Operation with incremental encoder and SMC30
p50083[D] = 5 The actual speed value comes from an incremental encoder connected to
an SMC30 (r3770).
p0400[1]
Encoder type selection
p2000
Speed in rpm at 100% speed
Remark:
The value set here determines the 100% speed for the closed-loop speed
control.
〈
5.6
〉
Operation with resolver and SMC10
p50083[D] = 5 A DRIVE-CLiQ encoder supplies the speed actual value
p0400[1]
Encoder type selection
p2000
Speed in rpm at 100% speed
Comment:
The value set here defines the 100% speed for the closed-loop speed
control.
〈
6
〉
Data for field
〈
6.1
〉
Control of the field
p50082 = 0
Internal field is not used
(e.g. in the case of permanent-magnet motors)
p50082 = 1
The field is activated with the line contactor
(field pulses are activated or deactivated at the same time as the line
contactor)
p50082 = 2
Automatic switching-in of the standstill field set using p50257 after a time
that can be parameterized using p50258 has elapsed, once operating state
o7 or higher has been reached
p50082 = 3
Field current permanently switched on
〈
6.2
〉
Field weakening
p50081 = 0
No speed-dependent or EMF-dependent field weakening
p50081 = 1
Field-weakening operation by means of internal closed-loop EMF control,
i.e. at speeds above the motor's rated speed (= "cut-in speed"), the motor
EMF is constantly kept at setpoint EMFset (r52289) = p50101 – p50100 x
p50110
〈
7
〉
Set basic technological functions
〈
7.1
〉
Current limits
p50171[D]
System current limit in torque direction I (as % of p50100)
p50172[D]
System current limit in torque direction II (as % of p50100)