52/348
Siemens Building Technologies
Basic Documentation RVP540 / RVP550
CE1P2488en
HVAC Products
Handling
18.10.2002
Line Function
Range
Unit
Resolution Factory
setting
Heating circuit EXP
700 Flow temperature setpoint boost mixing valve (UEM)
0...50 K
1
10
701 Gain factor of room influence (KORR)
0...20
–
1
4
702 Quick setback constant (KON)
(without room sensor)
0...20 –
1
2
703 Boost of room temperature setpoint
(with boost heating)
0...20 K
1
5
705 Type of control mixing valve
0 2-position
1 3-position
0 / 1
–
1
1
706 Switching differential mixing valve
(with 2-position mixing valves)
0...20 K
1
2
707 Overtemperature protection for the pump heating circuit
0 Inactive
1 Active
0 / 1
–
1
1
708 Heat
gains
-2...4
K
0.1
0
709 Adaption sensitivity 1
1...15
–
1
15
710 Adaption sensitivity 2
1...15
–
1
15
711 P-band heating circuit (Xp)
1...100
K
1
24
712 Integral action time heating circuit (Tn)
10...873
s
1
90
713 Actuator running time heating circuit
30...873
s
1
120
D.h.w. EXP
750 Maximum nominal setpoint of the d.h.w. temperature
(TBWmax)
8...80 °C
1
60
751 Switching differential of the d.h.w. temperature (SDBW) 0...20
K
1
5
752 d.h.w. discharge protection when charging with a wood-
fired boiler
1
Supervision of sensor of the wood-fired boiler
2
Supervision of sensors of the wood-fired boiler and of the
buffer storage tank
1 / 2
–
1
1
753 D.h.w. discharge protection when heating with the oil- /
gas-fired boiler
0 Not
active
1
Supervision of sensor of the oil- / gas-fired boiler
2
Supervision of sensors of the oil- / gas-fired boiler and of
the buffer storage tank
0...2 –
1
1
General / service EXP
800 Software
version
00.0...99.9
–
1
–
801 Device
operating
hours
0...999‘999
h
1
–
802 Resetting the EXP parameters
To reset the parameters of the EXP level to their default values, pres
the + / - buttons simultaneously for 3 seconds
0 / 1
–
1
0
803 Display of version of the basic diagram table
0...32‘767
–
1
–