Description of the heating engineer settings
18.10.2002
4
Description of the heating engineer
settings
For an overview of the settings and the setting procedure, refer to page 33.
General / service
Basic diagrams
Configure the controller as follows:
1. Select the required basic diagram from the library.
2. Select the basic diagram number.
3. Adapt the partial plant diagrams.
4. Hide the sensors that are not required.
5. Define the required auxiliary functions.
The basic diagrams and partial diagrams, a detailed description of the procedure to be
followed for the configuration, and additional information are given in the document
“Configuration and application”, documents no. CE1P2489en and CE1P2490en. In ad-
dition to the present document, that document is required to configure the controller.
Depending on the controller’s configuration,
parameter blocks that are not required will
be hidden.
If, for example, a basic diagram without a wood-fired boiler is selected, pa-
rameter block
“Wood-fired boiler”
with all its operating lines will be hidden.
If setting 0 is selected when selecting or adapting the partial diagrams, the respective
parameter blocks will also be hidden.
4.1
Selection of the basic diagram number
•
Straightforward basic configuration that matches the required plant diagram
The basic diagram selected from the basic diagram library (in document CE1P2489en
or CE1P2490en) can be configured by entering the basic diagram number.
1. Press the operating line selection buttons to select operating line 100.
2. Press the + / - buttons to select the required basic diagram number. The selected
number flashes on the display.
3. Confirm the selected basic diagram by pressing the + / - buttons
simultaneously
for 3 seconds. After confirmation, the display stops flashing.
Setting range
Unit
Factory setting
0...99.998 –
0
The selected basic diagram number will automatically be displayed on this operating
line. The basic diagram number is unambiguously assigned by the number of heat
sources and the type and number of available storage tanks. The key to the meaning of
the individual numbers is given in document CE1P2489en (2 heat sources) or docu-
ment CE1P2490en (3 heat sources).
Configuring the
controller
Required documents
Note
Benefit
Description
Setting
Effect