264/348
Siemens Building Technologies
Basic Documentation RVP540 / RVP550
CE1P2488en
HVAC Products
Description of the heating engineer settings
18.10.2002
•
Changeover of all controllers in the entire LPB system
Prerequisite:
–
Operating line 855 must be set to 1 (range of action = entire sys-
tem)
–
The contact must be connected to the master controller in
segment 0
Possible address: Device address 1
Segment address 0
(operating line 851)
Effect:
–
All controllers in the system switch to operating mode
–
With setting 0, d.h.w. heating is switched off in the entire system;
with setting 1, it is released in the entire system
–
With all controllers, operating mode changeover with the buttons is
no longer possible
–
When the contact of the remote telephone switch opens, all con-
trollers will return to the operating mode selected last
Check:
–
Buttons or +
flash on all controllers in the system
1)
1)
With setting 1 as selected above (d.h.w. heating locked), the two buttons and
will flash.
With setting 2 as selected above (d.h.w. heating remains released), only operating
mode button will flash.
•
Changeover of all controllers in the same segment
Prerequisite:
–
With segment 0, setting 0 must be made on operating line 855
(range of action of segment); with the other segments, the setting
on operating line 855 has no impact.
–
The contact must be connected to the master controller in seg-
ments 0 to 14
Possible addresses: Device address 1
Segment address 0...14 (operating line 851)
Effect:
–
All controllers in the same segment switch to operating mode
–
With setting 0, d.h.w. heating is switched off in the entire segment;
with setting 1, it is released in the entire segment
–
With all controllers in the same segment, operating mode change-
over with the buttons is no longer possible
–
When the contact of the remote telephone switch opens, all con-
trollers will return to the operating mode selected last
Check:
–
Buttons
or +
flash
on all controllers in the same segment
1)
1)
With setting 1 as selected above (d.h.w. heating locked), the two buttons and
will flash.
With setting 2 as selected above (d.h.w. heating remains released), only operating
mode button will flash.
Changeover of system
Changeover of segment