Description of the enduser settings
18.10.2002
3.5 Green
mode
•
Green
heating
mode
In the ”Green heating mode”, nonrenewable forms of energy will be locked.
In that case, the demand for heat will be covered by the wood-fired boiler and the solar collectors.
Activation:
Green mode is activated by pressing this button. It is accessible only
when the cover of the controller is open
Deactivation:
By pressing again the green button
During intermediate seasons, the demand for heat can possibly be covered by the solar
collectors and the wood-fired boiler. The conventional heat sources (oil / gas / electrical
immersion heaters / heat pump) will be locked.
Comfort losses – should they occur – will be accepted!
With operating parameter 801 (effect of the green button), it is possible to decide
whether the heat generation lock shall act when there is a demand for heat from d.h.w.,
the heating circuit, or from both. It is thus possible to define with which consumers
comfort losses – should they occur – will be accepted.
LED green mode is lit. The display does not change.
The green button has no impact on the frost protection function.
If green operation is triggered via input H1 (operating line 870), the LED will flash and
the green button is locked.
Benefit
Description
Setting
Effect
Note
Display
Important
Green operation via H1