18/348
Siemens Building Technologies
Basic Documentation RVP540 / RVP550
CE1P2488en
HVAC Products
Summary
18.10.2002
•
Protective boiler startup (acting on the consumers)
•
Minimum limitation of the boiler return temperature (acting on the mixing valve, by-
pass pump and / or consumers)
•
Protection against boiler overtemperature (pump overrun)
•
Adjustable minimum and maximum limitation of the boiler temperature
•
Cycling protection for heat generation
•
Frost protection for the building and the plant
•
Frost protection for the boiler and the d.h.w. storage tank connected directly to the
controller
•
Pump protection through periodic pump kick
•
Overtemperature protection for the pump heating circuit
•
Overtemperature protection for the storage tanks and the collector circuit
•
Room temperature adjustment with setpoint knob
•
Automatic button for efficient automatic operation throughout the year
•
Operating
mode
buttons
•
Button for green mode
•
Info button for additional information about the plant values
•
D.h.w.
button
•
Manual operation via manual operation button
•
7-day or 24-hour program for the heating circuit and d.h.w. heating
•
Remote operation via digital room unit
•
Output and input tests to aid commissioning and functional checks
•
Change of operating mode via a remote switch (via contact H1)
•
Service connection facility for local parameter settings and data logging
•
Holiday
program
•
D.h.w. heating with charging pump
•
D.h.w. control with temperature sensor or control thermostat
•
Selectable priority for d.h.w. heating
•
Selectable d.h.w. heating program
•
Adjustable boost of the d.h.w. charging temperature
•
Reduced setpoint of the d.h.w. temperature
•
Protection against discharging of d.h.w.
•
Automatic d.h.w. push
•
Legionella
function
•
Storage tank charge transfer with pump
•
Manual
d.h.w.
push
•
Communication via the Local Process Bus (LPB)
•
Communicating via PPS (BMU / room unit)
•
Controllers of other manufacture can deliver their heat demand signal by closing
potential-free contact H1
•
Controllers of other manufacture can deliver their analog heat demand by using
DC 0...10 V signals
•
Integrity of system architecture with all RVP... controllers
•
Can be extended to include 40 heating circuits (with central bus power supply)
•
Optional remote supervision
•
Error messages (own faults, faults of LPB devices, faults of PPS devices)
•
Logging the individual burner operating hours
•
Logging the number of burner starts
•
Logging the number of device operating hours
•
Logging the number of pump operating hours
Protection for the plant
Operation
D.h.w.
Use in extensive
systems
Logging