2.5 Parameter settings for the enduser
The following settings can be made to meet the individual needs of the enduser.
Buttons
Explanation
Line
1
Press one of the line selection buttons.
This will take you directly to the programming mode
"Enduser”.
2
Press the line selection buttons to select the required
line.
The parameter list on the next pages contains all set-
tings that can be made.
• • •
3
Press the + or - button to set the required value.
The setting will be stored as soon as you leave the
programming mode or change to another line.
4
By pressing any of the operating mode buttons, you
leave the programming mode "Enduser”.
Note:
If no button is pressed for about 8 minutes, the con-
troller will automatically return to the operating mode
selected last.
Continuous
display
Description
Setting