Description of the heating engineer settings
18.10.2002
4.4
Selection of partial diagram “Wood-fired
boiler”
The partial diagram “Wood-fired boiler” defined by the basic diagram can be replaced
by another partial diagram that requires the same number of terminals at the most, or it
can be hidden.
Setting range
Unit
Factory setting
0...5 –
0
The currently selected partial diagram number will automatically be displayed on this
operating line. The numbers have the following meaning:
0
No partial diagram selected.
Parameter block
“Wood-fired boiler”
will be hidden.
The basic diagram number remains the same.
The setting is useful when replacing the heat source or when a section of the
plant is already in operation and the wood-fired boiler is supplied later.
1...5
Partial diagrams according to the partial diagram library (documents
CE1P2489en and CE1P2490en).
4.5
Selection of partial diagram “Heat pump”
The partial diagram “Heat pump” defined by the basic diagram can be replaced by an-
other partial diagram that requires the same maximum number of terminals, or it can be
hidden.
Setting range
Unit
Factory setting
0...5 –
0
The currently selected partial diagram number will automatically be displayed on this
operating line. The numbers have the following meaning:
0
No partial diagram selected.
Parameter block
“Heat pump“
will be hidden.
The basic diagram number remains the same.
The setting is useful when replacing the heat source or when a section of the
plant is already in operation and the heat pump is supplied later.
1...5
Partial diagrams according to the partial diagram library (documents
CE1P2489en and CE1P2490en).
Description
Setting
Effect
Description