65/348
Siemens Building Technologies
Basic Documentation RVP540 / RVP550
CE1P2488en
HVAC Products
Description of the enduser settings
18.10.2002
0 2 4 6 8 10 12 14 16 18 20 22 24 h
2
373
Z
12
Sa
Mo
Tu
We
Th
Fr
Su
3.11 Switching times
With this setting, you determine the switching times for space heating. At these switch-
ing times, the temperature setpoints of the heating circuit change.
The heating program thus set becomes active when selecting automatic mode
.
Setting range
Unit
Factory setting
- -:- - / 00:00...24:00
h : min
See "Program overview"
below
First, select the weekday (operating line 5) for which the switching times shall be en-
tered!
The controller then makes a check to ensure the entries have been made in the correct
order.
At the times entered, the program will switch to the respective temperature setpoints.
The table below shows at what times which setpoints will be activated.
Entry:
– – : – –
Switching point inactive.
00:00...24:00
At the time entered, heating to the respective temperature is ensured.
Example:
Description
Setting
• • •
Important
Note
Effect