Handling
18.10.2002
Line Function
Range
Unit
Resolution Factory
setting
Speed-controlled pump
345 Display of speed of solar pump Q5 / K9
0...100
%
1
–
346 Minimum speed of the solar pump
0…line 347
%
1
40
347 Maximum speed of the solar pump
Line 346…100
% 1 100
Diagnosis
349 Functional test solar
--- No
test
0 Everything
OFF
1 Q5
ON
2
Q5/K12 + Q16 ON
3
Q5/K12 + Q16 + K9 ON
4
Q5/K12 + Q16 + K9 + K8 ON
--- / 0...4
–
1
- - -
Wood-fired boiler
Setpoints / actual values
350 Display of the boiler temperature setpoint
0...140
°C
1
–
351 Display of actual value of boiler temperature B22
--- No
value
available
-50...350 °C 1 –
352 Display of setpoint of the boiler return temperature
0...140
°C
1
–
353 Display of actual value of return temperature B72
--- No
value
available
-50...350 °C 1 –
Hours run counter
354 Operating hours pump of wood-fired boiler (output Q10)
To reset to 0, press the + / - buttons simultaneously for 3 seconds
0...999‘999 h
1
0
355 Operating hours pump of wood-fired boiler (output K3)
To reset to 0, press the + / - buttons simultaneously for 3 seconds
0...999‘999 h
1
0
356 Number of releases wood-fired boiler (output K3)
To reset to 0, press the + / - buttons simultaneously for 3 seconds
0...999‘999 –
1
0
Functions
369 Minimum temperature differential of the wood-fired boiler
0...20
K
1
4
370 Minimum temperature of wood-fired boiler for release of
pump
20...80 °C 1 60
371 Switching differential for minimum temperature of wood-
fired boiler for release of pump
1...30 K 1
12
372 Pump overrun time
---
No pump overrun time
--- / 4...120
min
1
20
373 Strategy
for
wood-fired
boiler
0 Constant
1 Depending
on
demand
0 / 1
–
1
1
376 Wood-fired boiler locks other heat sources
0 No
1 Yes
0 / 1
–
1
1
378 Frost protection for the plant with pump of the wood-
fired boiler
0
General frost protection for the plant does not act on this pump
1
General frost protection for the plant acts on this pump
0 / 1
–
1
1
Residual heat function
385 Maximum duration of residual heat function
--- Function
OFF
--- / 5...60
min
1
- - -
386 Perform residual heat function once / several times
0 Once
1 Several
times
0 / 1
–
1
0
387 Residual heat function with buffer storage tank stratifi-
cation protection
0 No
1 Yes
0 / 1
–
1
0
388 Residual heat function directly for the consumers
0 No
1 Yes
0 / 1
–
1
0
Speed-controlled pump
390 Display of speed of pump Q10 of the wood-fired boiler
0...100
%
1
–
391 Minimum speed of pump of the wood-fired boiler
0…line 392
%
1
50
392 Maximum speed of pump of the wood-fired boiler
Line 391…100
% 1 100