Description of the heating engineer settings
18.10.2002
4.82 Temperature differential swimming pool OFF
Swimming pool heating will be stopped when the temperature differential between col-
lector (B6 / B61) and swimming pool (B13) is too small.
Setting range
Unit
Factory setting
0... Line 319
K
4
As soon as the temperature differential is smaller than the value adjusted on this oper-
ating line, swimming pool heating will be stopped.
4.83 Maximum swimming pool charging
temperature
•
Maximum limitation of the water temperature in the swimming pool
The swimming pool temperature adjusted here is the maximum to which the water is
heated.
Setting range
Unit
Factory setting
20...95 °C
35
Charging will be stopped as soon as the maximum swimming pool charging tempera-
ture is reached.
Any surplus energy from the solar collectors will be delivered to the buffer / d.h.w. stor-
age tank until their safety temperature is reached and overtemperature protection de-
vices, if fitted, will respond.
4.84 Heat exchanger pump operation for
swimming pool
•
Optional alternative or parallel operation of storage tank and swimming pool heating
You can choose whether the swimming pool shall be heated at the same time as the
storage tanks or afterwards.
Setting range
Unit
Factory setting
1 / 2
–
1
The temperature differentials on operating lines 329 through 332 serve as the switch-on
/ off criteria for the storage tanks, and the temperature differentials on operating lines
319 and 320 for the swimming pool.
The setting on this operating line has the following effect:
1
Alternatively
The energy from the solar collectors is delivered either to one of the storage tanks
or to the swimming pool.
Which of the storage tanks is charged first depends on the priority selected on op-
erating line 333.
Description
Setting
Effect
Benefit
Description
Setting
Effect
Benefit
Description
Setting
Effect