HVAC Products
Description of the heating engineer settings
18.10.2002
0
No basic diagram number selected.
When confirming partial diagram 0, all parameters (with the exception
of the device operating hours) will be reset to their default values.
1.000... 99.998 Basic diagram numbers according to the basic diagram library.
Parameter blocks that are not required will be hidden.
Any change of the basic diagram resets all partial diagram and auxiliary function set-
tings as well as the reduction parameters (operating lines 120…193)!
Configuration
Partial diagrams
The selection on the operating lines only shows the possible partial diagrams. Partial
diagrams incompatible with the basic diagram or partial diagrams requiring more termi-
nal spaces than the original partial diagram will not be displayed.
This means that when “scrolling” through the partial diagrams with the + / - buttons,
jumps across one or several partial diagram numbers can occur.
For drawings of the individual partial diagrams, refer to the partial diagram library in the
documents “Configuration and application”:
•
CE1P2489en (for plants with 1 or 2 heat sources)
•
CE1P2490en (for plants with 3 heat sources)
When selecting a basic diagram (operating line 100), the partial diagrams will automati-
cally be set to the respective value.
4.2
Selection of partial diagram “Oil- / gas-fired
boiler”
The partial diagram with the oil-fired / gas-fired boiler defined by the basic diagram can
be replaced by another partial diagram with the same maximum number of terminals, or
it can be hidden.
Setting range
Unit
Factory setting
0...9 –
0
The currently selected partial diagram number will automatically be displayed on this
operating line. The numbers have the following meaning:
0
No partial diagram selected.
Parameter block
“Oil- / gas-fired boiler”
will be hidden.
The basic diagram number remains the same.
The setting is useful when the heat source is replaced or when part of the plant
is already in operation and the oil-fired / gas-fired boiler will be supplied later.
1...9
Partial diagrams according to the partial diagram library (documents
CE1P2489en and CE1P2490en).
Caution!
Caution!
General
Note
Description
Setting
Effect