Basic Documentation RVP540 / RVP550
CE1P2488en
HVAC Products
Description of the enduser settings
18.10.2002
Line
Switching point
Temperature setpoint
Standard
Switch-on time period 1
Setpoint of knob
06:00
Switch-off time period 1
Reduced setpoint
22:00
Switch-on time period 2
Setpoint of knob
– – : – –
Switch-off time period 2
Reduced setpoint
– – : – –
Switch-on time period 3
Setpoint of knob
– – : – –
Switch-off time period 3
Reduced setpoint
– – : – –
The time switch program can be set with the QAW70 room unit.
But this is possibly only if operating mode Auto
is selected on the controller.
Free time switch program
•
The free time switch program serves as a switching criterion for a number of func-
tions.
The time switch program consists of switching times that can be entered for the week-
days or the 7-day block.
It operates independently of the time switch programs for space heating and d.h.w.
The free time switch program can have an impact on the following functions:
•
Forced charging of the buffer storage tank with the heat pump (operating line 475)
•
D.h.w. circulating pump (operating line 772)
•
Auxiliary functions 23, K13 (operating line 169)
•
Additional pump kick for water / brine pump (operating line 427)
3.12 Preselection of weekday
With this setting, you select the weekdays or the 7-day block for which the switching
times of the time switch program apply.
Setting range
Unit
1-7
1...7
7-day block
Individual days
The principle is the same as that used with "Time switch program space heating" (refer
to the diagrams and the tip on page 64).
3.13 Switching times
With this setting, you define the switching times for the free time switch program.
Setting range
Unit
Factory setting
- -:- - / 00:00...24:00
h : min
See "Program overview"
below
First, select the weekday (operating line 12) for which the switching times shall be en-
tered!
Program overview
Effect of room unit
Benefit
Description
Description
Setting
Example:
Description
Setting
• • •
Important