Siemens Building Technologies
Basic Documentation RVP540 / RVP550
CE1P2488en
HVAC Products
Description of the heating engineer settings
18.10.2002
4.38 Electric immersion heater K6 for the d.h.w.
storage tank (ZuFu25)
•
Reheating the d.h.w. without putting the heating into operation
•
Frost protection for the d.h.w. or combi storage tank
The electric immersion heater makes possible
d.h.w. heating
without putting an addi-
tional heat source into operation. The electric immersion heater can provide d.h.w.
heating on its own or, if a solar collector is used, can reheat the d.h.w. to the current
setpoint, if required (according to the d.h.w. time switch program, refer to operating
lines 520 and 521).
However, the electric immersion heater can also be defined only for ensuring
frost pro-
tection for the d.h.w. storage tank
or the
combi storage tank
.
Setting range
Unit
Factory setting
--- / 101...110
K6
---
The auxiliary function is activated as soon as electric immersion heater K6 is assigned
a free terminal:
101...110 Electric
immersion
heater
K6
can be assigned to a free relay terminal
between Q101 and Q110.
---
No assignment made and the auxiliary function is not activated.
The electric immersion heater can be locked when the green button is activated, de-
pending on the parameterization of the green button.
The electric immersion heater
must
be connected in series with a safety limit thermo-
stat.
The electric immersion heater can be integrated in the diagram as follows:
Example:
B3
B31
BwSp 3
Q3
K6
ZuFu 25
23
93
Z0
5
Benefit
Description
Setting
Assignment
Note
Important
Application example