34/348
Siemens Building Technologies
Basic Documentation RVP540 / RVP550
CE1P2488en
HVAC Products
Handling
18.10.2002
2.6.1 Overview of heating engineer parameters
Line Function
Range
Unit
Resolution Factory
setting
General / service
Basic diagrams
100 Selection of basic diagram
0
No basic diagram selected
1...99.998 basic
diagrams
To adopt the selected basic diagram number, press the + / - buttons
simultaneously for 3 seconds.
0...99.998 –
1
0
Configuration
Partial diagrams
120 Selection of partial diagram “Oil-/ gas-fired boiler”
0
Partial diagram inactive (OeG0)
1...9 Partial diagrams OeG1 through OeG9
0...9 –
1
0
121 Selection of partial diagram “Solar collector”
0
Partial diagram not active (OeG0)
1...16 Partial diagrams Sol1 through Sol16
0...16 – 1
0
122 Selection of partial diagram “Wood-fired boiler”
0
Partial diagram not active (Ho0)
1...5 Partial diagrams Ho1 through Ho5
0...5 –
1
0
123 Selection of partial diagram “Heat pump”
0
Partial diagram not active (Wp0)
1...5
Partial diagrams Wp1 through Wp5
0...5 –
1
0
124 Display of partial diagram “Buffer storage tank”
0
Partial diagram not active (Sp0)
1...3 Partial diagrams Sp1 through Sp3
0...3 –
1
0
125 Display of partial diagram “D.h.w. storage tank”
0
Partial diagram not active (BwSp0)
1...10 Partial diagrams BwSp1 through BwSp10
0...10 – 1
0
126 Display of partial diagram “Combi storage tank”
0
Partial diagram not active (KoSp0)
1...6 Partial diagrams KoSp1 through KoSp6
0...6 –
1
0
127 Selection of partial diagram “Heating circuit”
0
Partial diagram not active (Rh0)
1...3 Partial diagrams Rh1 through Rh3
0...3 –
1
0
Hiding sensors that are not required
130 Source “Outside sensor”
0
Delivery via bus (PPS or LPB)
1 Delivery
via
connection
terminal
0 / 1
–
1
0
131 Reduction first d.h.w. temperature sensor B3
0
Without sensor B3
1 With
sensor
B3
0 / 1
–
1
0
132 Reduction second d.h.w. temperature sensor B31
0
Without sensor B31
1 With
sensor
B31
0 / 1
–
1
0
133 Reduction second buffer storage tank sensor B41
0
Without sensor B41
1 With
sensor
B41
0 / 1
–
1
0
135 Reduction return sensor B72 of wood-fired boiler
0
Without sensor B72
1 With
sensor
B72
0 / 1
–
1
0
136 Reduction heat pump flow sensor B21
0
Without sensor B21
1 With
sensor
B21
0 / 1
–
1
0
137 Reduction heat pump return sensor B71
0
Without sensor B71
1 With
sensor
B71
0 / 1
–
1
0
138 Reduction water / brine sensor B11
0
Without sensor B11
1 With
sensor
B11
0 / 1
–
1
0