Description of the heating engineer settings
18.10.2002
So that the heat sources are always released, setting "---" must be selected on the re-
spective operating lines (standard setting).
20
10
0
-10
-20
30
°C
23
92
Z
61
TAx
ged
OeG
Wp
-30
Bivalent-parallel and bivalent-partially-parallel operation is not possible with partial dia-
grams OeG9, Wp5 and Ho5.
4.190 Release of oil- / gas-fired boiler below the
outside temperature threshold
•
The outside temperature for release of the oil- / gas-fired boiler can be defined
Definition of the outside temperature
below
which the oil- / gas-fired boiler may be put
into operation.
Setting range
Unit
Factory setting
--- / -30...30
°C
- - -
---
Oil- / gas-fired boiler is always released
The oil- / gas-fired boiler is released when the composite outside temperature lies be-
low the adjusted value. If the outside temperature lies above the adjusted value, the oil-
/ gas-fired boiler is locked.
The switching points for release and locking are separated by a switching differential to
absorb small outside temperature variations.
Refer to “Release of outside temperature” (before operating line 630).