The device's ability to respond to material level changes is designed to exceed even the
most demanding installation requirements.
The Response rate (2.3.4.) (Page 174) setting automatically presets various parameters
affecting the device response to material level changes as follows:
Parameter (Units)
Values dependent on response rate
Slow
Medium
Fast
LOE timer (2.4.2.) (Page 177) (min)
100
10
1
Fill rate/minute (2.3.2.) (Page 173) (m/min)
0.1
1
10
Empty rate/minute (2.3.3.) (Page 173)
(m/min)
0.1
1
10
Filling indicator (2.3.9.) (Page 176) (m/min)
0.01
0.1
1
Emptying indicator (2.3.10.) (Page 176)
(m/min)
0.01
0.1
1
Rate filter (2.3.5.) (Page 175) (option)
10 min. or 300
mm (11.8 inch)
*1 min or 50 mm
(2 inch)
*1 min or 50
mm (2 inch)
Fuzz filter (2.11.5.6.) (Page 236) (% of span) 100
50
10
Echo lock window (2.11.5.5.) (Page 235)
(per Empty rate/minute (2.3.3.) (Page 173) /Filling
indicator (2.3.9.) (Page 176) and time since last valid
measurement)
Scan delay (2.1.14.) (Page 167) (seconds)
5
5
3
Number of long shots (2.1.12.) (Page 167)
10
5
2
If any of these parameters are independently altered, a Response rate (2.3.4.) (Page 174)
parameter alteration automatically resets the independently altered value.
Slower Response rate (2.3.4.) (Page 174) provides greater measurement reliability.
Faster performance may be obtained by independently setting Fill rate/minute (2.3.2.)
(Page 173) and Empty rate/minute (2.3.3.) (Page 173). Maximum rates may be impeded by
Echo lock (2.11.5.4.) (Page 235),Scan delay (2.1.14.) (Page 167) and Shot delay (2.1.16.)
(Page 168) values.
A.12
Analog output
The mA output (current output) is proportional to material level in the range 4 to 20 mA. 0%
and 100% are percentages of the full-scale reading (m, cm, mm, ft, in). Typically, mA output
is set so that 4 mA equals 0% and 20 mA equals 100%.
Содержание HydroRanger 200 HMI
Страница 2: ......
Страница 20: ...Introduction 1 5 Notes on warranty HydroRanger 200 HMI 18 Operating Instructions 06 2018 A5E36281317 AC ...
Страница 24: ...Safety notes HydroRanger 200 HMI 22 Operating Instructions 06 2018 A5E36281317 AC ...
Страница 28: ...Description 3 5 Modbus communication HydroRanger 200 HMI 26 Operating Instructions 06 2018 A5E36281317 AC ...
Страница 159: ...Parameter reference 8 2 Parameter indexing HydroRanger 200 HMI Operating Instructions 06 2018 A5E36281317 AC 157 ...
Страница 276: ...Parameter reference 8 10 Language 6 HydroRanger 200 HMI 274 Operating Instructions 06 2018 A5E36281317 AC ...
Страница 322: ...Pump control reference B 13 Other pump controls HydroRanger 200 HMI 320 Operating Instructions 06 2018 A5E36281317 AC ...
Страница 352: ...Communications C 41 Single parameter access SPA HydroRanger 200 HMI 350 Operating Instructions 06 2018 A5E36281317 AC ...
Страница 354: ...Updating software HydroRanger 200 HMI 352 Operating Instructions 06 2018 A5E36281317 AC ...
Страница 359: ...HydroRanger 200 HMI Operating Instructions 06 2018 A5E36281317 AC 357 Conduit entry for Class I Div 2 applications F ...
Страница 360: ...Conduit entry for Class I Div 2 applications HydroRanger 200 HMI 358 Operating Instructions 06 2018 A5E36281317 AC ...
Страница 361: ...Conduit entry for Class I Div 2 applications HydroRanger 200 HMI Operating Instructions 06 2018 A5E36281317 AC 359 ...
Страница 362: ......
Страница 372: ...Programming chart G 1 Programming chart HydroRanger 200 HMI 370 Operating Instructions 06 2018 A5E36281317 AC ...
Страница 390: ...LCD menu structure H 1 LCD Menu Structure HydroRanger 200 HMI 388 Operating Instructions 06 2018 A5E36281317 AC ...
Страница 403: ......