Parameter reference
8.6 Setup (2.)
HydroRanger 200 HMI
Operating Instructions, 06/2018, A5E36281317-AC
167
8.6.1.12
Number of long shots (2.1.12.)
Sets the number of long shots to be fired (and results averaged) per transmit pulse.
Index
Single-point model
Dual-point model
Global
Transducer
Values
Range: 0 to 200
Preset: 5
Response rate (2.3.4.) (Page 174)
Related
•
Number of short shots (2.1.11.) (Page 166)
•
Long shot frequency (2.1.8.) (Page 165)
•
Short shot duration (2.1.9.) (Page 166)
This value is automatically altered by Response rate (2.3.4.) (Page 174)
8.6.1.13
Shot synchro (2.1.13.)
Enables the System Sync on the terminal block.
Index
Global
Options
Not required
*Synchronized level monitors
Use this if another level measurement system is mounted nearby, and wired together on the
Sync terminal.
8.6.1.14
Scan delay (2.1.14.)
Adjusts the delay between measurements from transducer points, in seconds. Dual-point
model only.
Index
Global
Values
Range: 0 to 60 seconds
Preset: 5
Altered by
Response rate (2.3.4.) (Page 174)
Related
Sensor mode (2.1.3.) (Page 163)
This feature may only be used to adjust the delay before the next point is scanned. This
value is automatically altered when Response Rate (2.3.4.) (Page 174) is altered.
Содержание HydroRanger 200 HMI
Страница 2: ......
Страница 20: ...Introduction 1 5 Notes on warranty HydroRanger 200 HMI 18 Operating Instructions 06 2018 A5E36281317 AC ...
Страница 24: ...Safety notes HydroRanger 200 HMI 22 Operating Instructions 06 2018 A5E36281317 AC ...
Страница 28: ...Description 3 5 Modbus communication HydroRanger 200 HMI 26 Operating Instructions 06 2018 A5E36281317 AC ...
Страница 159: ...Parameter reference 8 2 Parameter indexing HydroRanger 200 HMI Operating Instructions 06 2018 A5E36281317 AC 157 ...
Страница 276: ...Parameter reference 8 10 Language 6 HydroRanger 200 HMI 274 Operating Instructions 06 2018 A5E36281317 AC ...
Страница 322: ...Pump control reference B 13 Other pump controls HydroRanger 200 HMI 320 Operating Instructions 06 2018 A5E36281317 AC ...
Страница 352: ...Communications C 41 Single parameter access SPA HydroRanger 200 HMI 350 Operating Instructions 06 2018 A5E36281317 AC ...
Страница 354: ...Updating software HydroRanger 200 HMI 352 Operating Instructions 06 2018 A5E36281317 AC ...
Страница 359: ...HydroRanger 200 HMI Operating Instructions 06 2018 A5E36281317 AC 357 Conduit entry for Class I Div 2 applications F ...
Страница 360: ...Conduit entry for Class I Div 2 applications HydroRanger 200 HMI 358 Operating Instructions 06 2018 A5E36281317 AC ...
Страница 361: ...Conduit entry for Class I Div 2 applications HydroRanger 200 HMI Operating Instructions 06 2018 A5E36281317 AC 359 ...
Страница 362: ......
Страница 372: ...Programming chart G 1 Programming chart HydroRanger 200 HMI 370 Operating Instructions 06 2018 A5E36281317 AC ...
Страница 390: ...LCD menu structure H 1 LCD Menu Structure HydroRanger 200 HMI 388 Operating Instructions 06 2018 A5E36281317 AC ...
Страница 403: ......