Parameter reference
8.6 Setup (2.)
HydroRanger 200 HMI
196
Operating Instructions, 06/2018, A5E36281317-AC
Control
Type
Relay control
*OFF
Relay set off, no action (preset).
Level
Based on level setpoints ON and OFF.
Alarm
Low Low Alarm
Low Alarm
High Alarm
High High Alarm
General
In-bounds
When level enters the range between ON and
OFF setpoints.
Out-of-bounds
When level exits the range between ON and
OFF setpoints.
Rate of Change
Based on rate setpoints ON and OFF.
Temperature
Based on temperature setpoints ON and OFF.
LOE
Loss of echo; when echo is lost.
Cable Fault
When the circuit to a transducer is opened.
Flow
Totalizer
Every 10
y
units [Mantissa (2.10.2.2.)
(Page 213) - Relay Duration (2.10.2.4.)
(Page 215)]
Flow Sampler
Every y x 10
2
units [Mantissa (2.10.2.2.)
(Page 213) - Relay Duration (2.10.2.4.)
(Page 215)] or time duration [Relay Interval
Setpoint (2.10.2.6.) (Page 215)]
Pump
Fixed Duty Assist
At fixed ON and OFF setpoints and allows
multiple pumps to run or for rake control.
Fixed Duty Backup
At fixed ON and OFF setpoints and allows only
one pump to run.
Alternate Duty Assist
At rotating ON and OFF setpoints and allows
multiple pumps to run.
Alternate Duty Backup
At rotating ON and OFF setpoints and allows
only one pump to run.
Service Ratio Duty Assist
On service ratio at ON and OFF setpoints and
allows multiple pumps to run.
Service Ratio Duty Backup
On service ratio at ON and OFF setpoints and
allows only one pump to run.
First In First Out
As Alternate Duty Assist, resets the relay from
staggered OFF setpoints.
Control
Flush Valve
Used to control a pump flushing device based
on Flush Systems [Flush pump (2.10.3.2.)
(Page 216) to Flush duration (2.10.3.5.)
(Page 217)].
Communication
Based on input from external communications.
For more information, see Modbus register
Содержание HydroRanger 200 HMI
Страница 2: ......
Страница 20: ...Introduction 1 5 Notes on warranty HydroRanger 200 HMI 18 Operating Instructions 06 2018 A5E36281317 AC ...
Страница 24: ...Safety notes HydroRanger 200 HMI 22 Operating Instructions 06 2018 A5E36281317 AC ...
Страница 28: ...Description 3 5 Modbus communication HydroRanger 200 HMI 26 Operating Instructions 06 2018 A5E36281317 AC ...
Страница 159: ...Parameter reference 8 2 Parameter indexing HydroRanger 200 HMI Operating Instructions 06 2018 A5E36281317 AC 157 ...
Страница 276: ...Parameter reference 8 10 Language 6 HydroRanger 200 HMI 274 Operating Instructions 06 2018 A5E36281317 AC ...
Страница 322: ...Pump control reference B 13 Other pump controls HydroRanger 200 HMI 320 Operating Instructions 06 2018 A5E36281317 AC ...
Страница 352: ...Communications C 41 Single parameter access SPA HydroRanger 200 HMI 350 Operating Instructions 06 2018 A5E36281317 AC ...
Страница 354: ...Updating software HydroRanger 200 HMI 352 Operating Instructions 06 2018 A5E36281317 AC ...
Страница 359: ...HydroRanger 200 HMI Operating Instructions 06 2018 A5E36281317 AC 357 Conduit entry for Class I Div 2 applications F ...
Страница 360: ...Conduit entry for Class I Div 2 applications HydroRanger 200 HMI 358 Operating Instructions 06 2018 A5E36281317 AC ...
Страница 361: ...Conduit entry for Class I Div 2 applications HydroRanger 200 HMI Operating Instructions 06 2018 A5E36281317 AC 359 ...
Страница 362: ......
Страница 372: ...Programming chart G 1 Programming chart HydroRanger 200 HMI 370 Operating Instructions 06 2018 A5E36281317 AC ...
Страница 390: ...LCD menu structure H 1 LCD Menu Structure HydroRanger 200 HMI 388 Operating Instructions 06 2018 A5E36281317 AC ...
Страница 403: ......