Commissioning
6.6 Requesting an echo profile
HydroRanger 200 HMI
86
Operating Instructions, 06/2018, A5E36281317-AC
Configure another relay
Gives option to configure more relays or end the wizard.
Options
YES
Returns to the Relay Function menu
NO
Completes the QS Pump Control configuration
End of QS Volume Wizard
Note
For QS to be successful, all changes must be applied.
Options
BACK, CANCEL, FINISH
Display returns to 1.1 Quick Start menu when Quick Start is successfully com-
pleted or cancelled. If CANCEL is selected, no changes are written to the device.
To transfer Quick Start values to the device and return to PROGRAM menu, press DOWN
arrow (Finish). Then press LEFT arrow three times to return to Measurement mode.
6.6
Requesting an echo profile
1.
In PROGRAM mode, navigate to: Main Menu > Diagnostics (3.2.) > Echo Profile (3.2.2.).
2.
Press RIGHT arrow to request a profile.
①
Confidence
1
②
Algorithm BLF (best of first or largest echo)
2
③
Distance from transducer to target
④
Echo
⑤
TVT
3.
Use UP or DOWN arrow to scroll to an icon. When an icon is highlighted, that
feature becomes active.
4.
To move a cursor, press RIGHT arrow to increase the value, LEFT arrow to
decrease.
Содержание HydroRanger 200 HMI
Страница 2: ......
Страница 20: ...Introduction 1 5 Notes on warranty HydroRanger 200 HMI 18 Operating Instructions 06 2018 A5E36281317 AC ...
Страница 24: ...Safety notes HydroRanger 200 HMI 22 Operating Instructions 06 2018 A5E36281317 AC ...
Страница 28: ...Description 3 5 Modbus communication HydroRanger 200 HMI 26 Operating Instructions 06 2018 A5E36281317 AC ...
Страница 159: ...Parameter reference 8 2 Parameter indexing HydroRanger 200 HMI Operating Instructions 06 2018 A5E36281317 AC 157 ...
Страница 276: ...Parameter reference 8 10 Language 6 HydroRanger 200 HMI 274 Operating Instructions 06 2018 A5E36281317 AC ...
Страница 322: ...Pump control reference B 13 Other pump controls HydroRanger 200 HMI 320 Operating Instructions 06 2018 A5E36281317 AC ...
Страница 352: ...Communications C 41 Single parameter access SPA HydroRanger 200 HMI 350 Operating Instructions 06 2018 A5E36281317 AC ...
Страница 354: ...Updating software HydroRanger 200 HMI 352 Operating Instructions 06 2018 A5E36281317 AC ...
Страница 359: ...HydroRanger 200 HMI Operating Instructions 06 2018 A5E36281317 AC 357 Conduit entry for Class I Div 2 applications F ...
Страница 360: ...Conduit entry for Class I Div 2 applications HydroRanger 200 HMI 358 Operating Instructions 06 2018 A5E36281317 AC ...
Страница 361: ...Conduit entry for Class I Div 2 applications HydroRanger 200 HMI Operating Instructions 06 2018 A5E36281317 AC 359 ...
Страница 362: ......
Страница 372: ...Programming chart G 1 Programming chart HydroRanger 200 HMI 370 Operating Instructions 06 2018 A5E36281317 AC ...
Страница 390: ...LCD menu structure H 1 LCD Menu Structure HydroRanger 200 HMI 388 Operating Instructions 06 2018 A5E36281317 AC ...
Страница 403: ......