Parameter reference
8.6 Setup (2.)
HydroRanger 200 HMI
Operating Instructions, 06/2018, A5E36281317-AC
217
Flush cycles (2.10.3.3.)
Sets the number of pump cycles requiring flush control.
Index
Single-point model
Dual-point model
Global
Relay
Values
Range: 0 ... 34464
Preset: 0
Related
Relay Function (2.8.1.4.) (Page 195) = Flush Valve
If three flush cycles are required after every ten pump cycles, then:
Flush Interval (2.10.3.4.) (Page 217) = 10
Flush Cycles (2.10.3.3.) = 3
Flush interval (2.10.3.4.)
Sets the number of pump cycles before flush control is enabled.
Index
Single-point model
Dual-point model
Global
Relay
Values
Range: 0 ... 37856
Preset: 0
Related
Relay Function (2.8.1.4.) (Page 195) = Flush Valve
To start a new flush cycle every ten times the pumps are run, set this to 10.
Flush duration (2.10.3.5.)
Sets the length of time for each flush cycle that the flush control is active.
Index
Single-point model
Dual-point model
Global
Relay
Values
Range: 0.000 ... 9999 seconds
Preset: 0.000 seconds
Related
Relay Function (2.8.1.4.) (Page 195) = Flush Valve
Содержание HydroRanger 200 HMI
Страница 2: ......
Страница 20: ...Introduction 1 5 Notes on warranty HydroRanger 200 HMI 18 Operating Instructions 06 2018 A5E36281317 AC ...
Страница 24: ...Safety notes HydroRanger 200 HMI 22 Operating Instructions 06 2018 A5E36281317 AC ...
Страница 28: ...Description 3 5 Modbus communication HydroRanger 200 HMI 26 Operating Instructions 06 2018 A5E36281317 AC ...
Страница 159: ...Parameter reference 8 2 Parameter indexing HydroRanger 200 HMI Operating Instructions 06 2018 A5E36281317 AC 157 ...
Страница 276: ...Parameter reference 8 10 Language 6 HydroRanger 200 HMI 274 Operating Instructions 06 2018 A5E36281317 AC ...
Страница 322: ...Pump control reference B 13 Other pump controls HydroRanger 200 HMI 320 Operating Instructions 06 2018 A5E36281317 AC ...
Страница 352: ...Communications C 41 Single parameter access SPA HydroRanger 200 HMI 350 Operating Instructions 06 2018 A5E36281317 AC ...
Страница 354: ...Updating software HydroRanger 200 HMI 352 Operating Instructions 06 2018 A5E36281317 AC ...
Страница 359: ...HydroRanger 200 HMI Operating Instructions 06 2018 A5E36281317 AC 357 Conduit entry for Class I Div 2 applications F ...
Страница 360: ...Conduit entry for Class I Div 2 applications HydroRanger 200 HMI 358 Operating Instructions 06 2018 A5E36281317 AC ...
Страница 361: ...Conduit entry for Class I Div 2 applications HydroRanger 200 HMI Operating Instructions 06 2018 A5E36281317 AC 359 ...
Страница 362: ......
Страница 372: ...Programming chart G 1 Programming chart HydroRanger 200 HMI 370 Operating Instructions 06 2018 A5E36281317 AC ...
Страница 390: ...LCD menu structure H 1 LCD Menu Structure HydroRanger 200 HMI 388 Operating Instructions 06 2018 A5E36281317 AC ...
Страница 403: ......