Connecting
5.7 Temperature sensor
HydroRanger 200 HMI
44
Operating Instructions, 06/2018, A5E36281317-AC
5.7
Temperature sensor
Accurate temperature readings are critical to accurate level measurements because the
speed of sound changes, depending on air temperature, and all Siemens Echomax and ST-
H transducers have an internal temperature sensor.
Having a separate TS-3 temperature sensor will ensure optimum accuracy if the following
conditions apply:
●
The transducer is exposed to direct sunlight (or other radiant heat source).
●
The transducer face and monitored surface temperature differs.
●
Faster response to temperature changes is required.
To achieve the best performance of temperature measurement in a typical open channel
flow application, the temperature sensor should be shielded from direct sunlight and
mounted halfway between the ultrasonic transducer face and the maximum head achievable
in the application. Care should be taken to avoid obstructing the direct sound path of the
ultrasonic transducer.
Note
Use a TS-3 Temperature Sensor only. Leave terminals open (unused) if TS-3 is not
deployed.
5.8
mA input
For more information, consult parameters Transducer (2.1.5.) (Page 164), mA input range
(2.6.1.) (Page 184), 0/4 mA level value (2.6.2.) (Page 184), and 20 mA level value (2.6.3.)
(Page 184).
Содержание HydroRanger 200 HMI
Страница 2: ......
Страница 20: ...Introduction 1 5 Notes on warranty HydroRanger 200 HMI 18 Operating Instructions 06 2018 A5E36281317 AC ...
Страница 24: ...Safety notes HydroRanger 200 HMI 22 Operating Instructions 06 2018 A5E36281317 AC ...
Страница 28: ...Description 3 5 Modbus communication HydroRanger 200 HMI 26 Operating Instructions 06 2018 A5E36281317 AC ...
Страница 159: ...Parameter reference 8 2 Parameter indexing HydroRanger 200 HMI Operating Instructions 06 2018 A5E36281317 AC 157 ...
Страница 276: ...Parameter reference 8 10 Language 6 HydroRanger 200 HMI 274 Operating Instructions 06 2018 A5E36281317 AC ...
Страница 322: ...Pump control reference B 13 Other pump controls HydroRanger 200 HMI 320 Operating Instructions 06 2018 A5E36281317 AC ...
Страница 352: ...Communications C 41 Single parameter access SPA HydroRanger 200 HMI 350 Operating Instructions 06 2018 A5E36281317 AC ...
Страница 354: ...Updating software HydroRanger 200 HMI 352 Operating Instructions 06 2018 A5E36281317 AC ...
Страница 359: ...HydroRanger 200 HMI Operating Instructions 06 2018 A5E36281317 AC 357 Conduit entry for Class I Div 2 applications F ...
Страница 360: ...Conduit entry for Class I Div 2 applications HydroRanger 200 HMI 358 Operating Instructions 06 2018 A5E36281317 AC ...
Страница 361: ...Conduit entry for Class I Div 2 applications HydroRanger 200 HMI Operating Instructions 06 2018 A5E36281317 AC 359 ...
Страница 362: ......
Страница 372: ...Programming chart G 1 Programming chart HydroRanger 200 HMI 370 Operating Instructions 06 2018 A5E36281317 AC ...
Страница 390: ...LCD menu structure H 1 LCD Menu Structure HydroRanger 200 HMI 388 Operating Instructions 06 2018 A5E36281317 AC ...
Страница 403: ......