Commissioning
6.5 Quick Start Wizards
HydroRanger 200 HMI
80
Operating Instructions, 06/2018, A5E36281317-AC
Maximum flow
The maximum flowrate associated with Maximum head (2.13.4.2.) (Page 243).
Index
Single-point model
Dual-point model
Global
Transducer
Values
Range: -999 ... 9999
Preset: 1000
This represents the flow at the highest head level supported by the PMD and works in
conjunction with Maximum head (2.13.4.2.) (Page 243) to define the highest point in the
exponential curve. Use it when the PMD requires a maximum head and flow reference point.
This would include Exponential, Palmer-Bowlus Flume, H-Flume, and Universal breakpoints.
Also, use this parameter with Flow time units (2.13.4.4.) (Page 244) to define the flowrate
units. The limitation of four digits is for the LCD only, and the flowrate value is available with
greater precision through communications.
Note
•
The display of the measured value is limited to six digits. A Maximum Flow value larger
than seven characters will not display correctly.
•
If measured value is larger than seven characters, the screen displays ####. A larger unit
[Flow time units (2.13.4.4.) (Page 244)] should be used, or number of decimal points
[Flowrate decimal (2.13.4.6.) (Page 245)] should be reduced.
Flowrate decimal
The maximum number of decimal places to be displayed.
Index
Single-point model
Dual-point model
Global
Transducer
Options
No digits
1 digit
*2 digits
3 digits
In RUN mode, the number of decimal places displayed is automatically adjusted (if
necessary) to prevent the number of Flowrate digits from exceeding display capabilities.
The maximum number of head decimal places is controlled by Decimal position (2.12.4.)
(Page 237)
Содержание HydroRanger 200 HMI
Страница 2: ......
Страница 20: ...Introduction 1 5 Notes on warranty HydroRanger 200 HMI 18 Operating Instructions 06 2018 A5E36281317 AC ...
Страница 24: ...Safety notes HydroRanger 200 HMI 22 Operating Instructions 06 2018 A5E36281317 AC ...
Страница 28: ...Description 3 5 Modbus communication HydroRanger 200 HMI 26 Operating Instructions 06 2018 A5E36281317 AC ...
Страница 159: ...Parameter reference 8 2 Parameter indexing HydroRanger 200 HMI Operating Instructions 06 2018 A5E36281317 AC 157 ...
Страница 276: ...Parameter reference 8 10 Language 6 HydroRanger 200 HMI 274 Operating Instructions 06 2018 A5E36281317 AC ...
Страница 322: ...Pump control reference B 13 Other pump controls HydroRanger 200 HMI 320 Operating Instructions 06 2018 A5E36281317 AC ...
Страница 352: ...Communications C 41 Single parameter access SPA HydroRanger 200 HMI 350 Operating Instructions 06 2018 A5E36281317 AC ...
Страница 354: ...Updating software HydroRanger 200 HMI 352 Operating Instructions 06 2018 A5E36281317 AC ...
Страница 359: ...HydroRanger 200 HMI Operating Instructions 06 2018 A5E36281317 AC 357 Conduit entry for Class I Div 2 applications F ...
Страница 360: ...Conduit entry for Class I Div 2 applications HydroRanger 200 HMI 358 Operating Instructions 06 2018 A5E36281317 AC ...
Страница 361: ...Conduit entry for Class I Div 2 applications HydroRanger 200 HMI Operating Instructions 06 2018 A5E36281317 AC 359 ...
Страница 362: ......
Страница 372: ...Programming chart G 1 Programming chart HydroRanger 200 HMI 370 Operating Instructions 06 2018 A5E36281317 AC ...
Страница 390: ...LCD menu structure H 1 LCD Menu Structure HydroRanger 200 HMI 388 Operating Instructions 06 2018 A5E36281317 AC ...
Страница 403: ......