Communications
C.36 Split values
HydroRanger 200 HMI
Operating Instructions, 06/2018, A5E36281317-AC
341
C.36
Split values
Certain parameters are actually pairs of numbers separated by a colon, using this format:
xx:yy.
One example is Echo Confidence as shown in Measurement View 2 [The local display
(Page 51)], where:
xx = the average noise value in dB
yy = the peak noise in dB
The number which corresponds to xx:yy, either for reading or setting a parameter, is
determined by the following formula:
For storing to the device:
value = (xx + 128) x 256 + (yy + 128)
For reading from the device:
xx = (value / 256) – 128
yy = (value % 256) – 128
where % is the modulus operator.
The modulus can be computed by following these steps:
value
1
= value / 256
value
2
= remainder of value
1
value
3
= value
2
x 256
yy = value
3
– 128
It may simplify parameter to notice:
xx = (most significant byte of value) – 128
yy = (least significant byte of value) – 128
Содержание HydroRanger 200 HMI
Страница 2: ......
Страница 20: ...Introduction 1 5 Notes on warranty HydroRanger 200 HMI 18 Operating Instructions 06 2018 A5E36281317 AC ...
Страница 24: ...Safety notes HydroRanger 200 HMI 22 Operating Instructions 06 2018 A5E36281317 AC ...
Страница 28: ...Description 3 5 Modbus communication HydroRanger 200 HMI 26 Operating Instructions 06 2018 A5E36281317 AC ...
Страница 159: ...Parameter reference 8 2 Parameter indexing HydroRanger 200 HMI Operating Instructions 06 2018 A5E36281317 AC 157 ...
Страница 276: ...Parameter reference 8 10 Language 6 HydroRanger 200 HMI 274 Operating Instructions 06 2018 A5E36281317 AC ...
Страница 322: ...Pump control reference B 13 Other pump controls HydroRanger 200 HMI 320 Operating Instructions 06 2018 A5E36281317 AC ...
Страница 352: ...Communications C 41 Single parameter access SPA HydroRanger 200 HMI 350 Operating Instructions 06 2018 A5E36281317 AC ...
Страница 354: ...Updating software HydroRanger 200 HMI 352 Operating Instructions 06 2018 A5E36281317 AC ...
Страница 359: ...HydroRanger 200 HMI Operating Instructions 06 2018 A5E36281317 AC 357 Conduit entry for Class I Div 2 applications F ...
Страница 360: ...Conduit entry for Class I Div 2 applications HydroRanger 200 HMI 358 Operating Instructions 06 2018 A5E36281317 AC ...
Страница 361: ...Conduit entry for Class I Div 2 applications HydroRanger 200 HMI Operating Instructions 06 2018 A5E36281317 AC 359 ...
Страница 362: ......
Страница 372: ...Programming chart G 1 Programming chart HydroRanger 200 HMI 370 Operating Instructions 06 2018 A5E36281317 AC ...
Страница 390: ...LCD menu structure H 1 LCD Menu Structure HydroRanger 200 HMI 388 Operating Instructions 06 2018 A5E36281317 AC ...
Страница 403: ......