Operating
7.3 Relays
HydroRanger 200 HMI
Operating Instructions, 06/2018, A5E36281317-AC
101
Wet Well 2
Pump down with the following level and rate settings:
Parameter
Relay #
1
2
3
4
5
6
(Page 195)
Alternate Duty
Assist
Alternate Duty
Assist
Level (H)
Level (L)
OFF
OFF
(Page 197)
70%
80%
90%
10%
--
--
(Page 197)
20%
20%
85%
15%
--
--
(Page 198)
ON
Pump by Rate (2.8.1.8.) (Page 198) sets the pump relays to accept control by rate of level change
once the first ON setpoint is reached. Because the pumps are started by rate, you must change Emp-
tying Indicator (2.3.10.) (Page 199) to desired empty rate.
Reservoir 1
Pump up with the following level settings:
Parameter
Relay #
1
2
3
4
5
6
(Page 195)
Alternate Duty
Assist
Alternate Duty
Assist
Level (H)
Level (L) OFF
OFF
(Page 197)
30%
20%
90%
10%
--
--
(Page 197)
80%
80%
85%
15%
--
--
Содержание HydroRanger 200 HMI
Страница 2: ......
Страница 20: ...Introduction 1 5 Notes on warranty HydroRanger 200 HMI 18 Operating Instructions 06 2018 A5E36281317 AC ...
Страница 24: ...Safety notes HydroRanger 200 HMI 22 Operating Instructions 06 2018 A5E36281317 AC ...
Страница 28: ...Description 3 5 Modbus communication HydroRanger 200 HMI 26 Operating Instructions 06 2018 A5E36281317 AC ...
Страница 159: ...Parameter reference 8 2 Parameter indexing HydroRanger 200 HMI Operating Instructions 06 2018 A5E36281317 AC 157 ...
Страница 276: ...Parameter reference 8 10 Language 6 HydroRanger 200 HMI 274 Operating Instructions 06 2018 A5E36281317 AC ...
Страница 322: ...Pump control reference B 13 Other pump controls HydroRanger 200 HMI 320 Operating Instructions 06 2018 A5E36281317 AC ...
Страница 352: ...Communications C 41 Single parameter access SPA HydroRanger 200 HMI 350 Operating Instructions 06 2018 A5E36281317 AC ...
Страница 354: ...Updating software HydroRanger 200 HMI 352 Operating Instructions 06 2018 A5E36281317 AC ...
Страница 359: ...HydroRanger 200 HMI Operating Instructions 06 2018 A5E36281317 AC 357 Conduit entry for Class I Div 2 applications F ...
Страница 360: ...Conduit entry for Class I Div 2 applications HydroRanger 200 HMI 358 Operating Instructions 06 2018 A5E36281317 AC ...
Страница 361: ...Conduit entry for Class I Div 2 applications HydroRanger 200 HMI Operating Instructions 06 2018 A5E36281317 AC 359 ...
Страница 362: ......
Страница 372: ...Programming chart G 1 Programming chart HydroRanger 200 HMI 370 Operating Instructions 06 2018 A5E36281317 AC ...
Страница 390: ...LCD menu structure H 1 LCD Menu Structure HydroRanger 200 HMI 388 Operating Instructions 06 2018 A5E36281317 AC ...
Страница 403: ......