Parameter reference
8.6 Setup (2.)
HydroRanger 200 HMI
Operating Instructions, 06/2018, A5E36281317-AC
207
Delay Between Starts (2.8.2.8.1.)
Sets the minimum delay (in seconds) between pump starts. This delay determines when the
next pump is permitted to start.
Index
Global
Values
Range: 0.0 ... 9999
Preset: 10 seconds
Related
•
Run-ON Interval (2.8.2.7.1.) (Page 205)
•
Power Resumption Delay (2.8.2.8.2.) (Page 207)
•
Level setpoint variation (2.8.2.6.2.) (Page 204)
•
Pump by rate (2.8.1.8.) (Page 198)
Power Resumption Delay (2.8.2.8.2.)
Sets the minimum delay before the first pump restarts after power failure.
Index
Global
Values
Range: 0.000 ... 9999
Preset: 10 seconds
Related
•
Run-ON Interval (2.8.2.7.1.) (Page 205)
•
Level setpoint variation (2.8.2.6.2.) (Page 204)
•
Pump by rate (2.8.1.8.) (Page 198)
•
Delay Between Starts (2.8.2.8.1.) (Page 207)
This reduces power surge by not having the first pump start immediately upon power
resumption. When this delay expires, other pumps will start as per Delay Between Starts
(2.8.2.8.1.) (Page 207).
8.6.9
Discrete Inputs (2.9.)
Discrete inputs can be used for the following:
●
Passing other information to a remote system through communications
●
Backup level override
Use the parameters listed above to have discrete inputs modify the unit’s operation. To
configure the discrete input itself, use the following parameters:
8.6.9.1
Backup Level Override (2.9.1.)
Overrides the transducer reading by a discrete input, such as a contacting point device. The
transducer reading will be fixed at the programmed override value until the discrete input is
released.
The device makes decisions based on the override values.
Содержание HydroRanger 200 HMI
Страница 2: ......
Страница 20: ...Introduction 1 5 Notes on warranty HydroRanger 200 HMI 18 Operating Instructions 06 2018 A5E36281317 AC ...
Страница 24: ...Safety notes HydroRanger 200 HMI 22 Operating Instructions 06 2018 A5E36281317 AC ...
Страница 28: ...Description 3 5 Modbus communication HydroRanger 200 HMI 26 Operating Instructions 06 2018 A5E36281317 AC ...
Страница 159: ...Parameter reference 8 2 Parameter indexing HydroRanger 200 HMI Operating Instructions 06 2018 A5E36281317 AC 157 ...
Страница 276: ...Parameter reference 8 10 Language 6 HydroRanger 200 HMI 274 Operating Instructions 06 2018 A5E36281317 AC ...
Страница 322: ...Pump control reference B 13 Other pump controls HydroRanger 200 HMI 320 Operating Instructions 06 2018 A5E36281317 AC ...
Страница 352: ...Communications C 41 Single parameter access SPA HydroRanger 200 HMI 350 Operating Instructions 06 2018 A5E36281317 AC ...
Страница 354: ...Updating software HydroRanger 200 HMI 352 Operating Instructions 06 2018 A5E36281317 AC ...
Страница 359: ...HydroRanger 200 HMI Operating Instructions 06 2018 A5E36281317 AC 357 Conduit entry for Class I Div 2 applications F ...
Страница 360: ...Conduit entry for Class I Div 2 applications HydroRanger 200 HMI 358 Operating Instructions 06 2018 A5E36281317 AC ...
Страница 361: ...Conduit entry for Class I Div 2 applications HydroRanger 200 HMI Operating Instructions 06 2018 A5E36281317 AC 359 ...
Страница 362: ......
Страница 372: ...Programming chart G 1 Programming chart HydroRanger 200 HMI 370 Operating Instructions 06 2018 A5E36281317 AC ...
Страница 390: ...LCD menu structure H 1 LCD Menu Structure HydroRanger 200 HMI 388 Operating Instructions 06 2018 A5E36281317 AC ...
Страница 403: ......