Diagnosing and troubleshooting
10.4 Noise problems
HydroRanger 200 HMI
288
Operating Instructions, 06/2018, A5E36281317-AC
Try moving the electronics to a different location. Often moving the electronics a few meters
farther from the source of noise will fix the problem. Shielding the electronics is also an
option, but it should be a last resort. Proper shielding is expensive and is difficult to install
properly–the shielding box must enclose the device electronics completely, and all wires
must be brought to the box through grounded metal conduit.
10.4.3
Avoiding common wiring problems
●
Make sure that the transducer shield wire is connected at the electronics end only. Do not
ground it at any other location.
●
Do not connect the transducer shield wire to the white wire.
●
The exposed transducer shield wire must be as short as possible.
●
Connections between the wire supplied with the transducer, and any customer installed
extension wire should only be grounded at the device.
●
On Siemens transducers the white wire is negative and the black wire is positive. If the
extension wire is colored differently, make sure that it is wired consistently.
●
Extension wire must be shielded twisted pair. See the installation section for
specifications.
10.4.4
Reducing electrical noise
●
Ensure that the transducer cable does not run parallel to other cables carrying high
voltage or current.
●
Move the transducer cable away from noise generators like variable speed drives.
●
Put the transducer cable in grounded metal conduit.
●
Filter the noise source.
●
Check grounding.
10.4.5
Reducing acoustical noise
●
Move the transducer away from the noise source.
●
Use a stilling well.
●
Install a rubber or foam bushing or gasket between the transducer and the mounting
surface.
●
Relocate or insulate the noise source.
●
Change the frequency of the noise. Ultrasonic devices are sensitive to noise in the
frequency range of the transducer employed.
●
Check that transducer is not mounted too tightly; only hand-tight.
Содержание HydroRanger 200 HMI
Страница 2: ......
Страница 20: ...Introduction 1 5 Notes on warranty HydroRanger 200 HMI 18 Operating Instructions 06 2018 A5E36281317 AC ...
Страница 24: ...Safety notes HydroRanger 200 HMI 22 Operating Instructions 06 2018 A5E36281317 AC ...
Страница 28: ...Description 3 5 Modbus communication HydroRanger 200 HMI 26 Operating Instructions 06 2018 A5E36281317 AC ...
Страница 159: ...Parameter reference 8 2 Parameter indexing HydroRanger 200 HMI Operating Instructions 06 2018 A5E36281317 AC 157 ...
Страница 276: ...Parameter reference 8 10 Language 6 HydroRanger 200 HMI 274 Operating Instructions 06 2018 A5E36281317 AC ...
Страница 322: ...Pump control reference B 13 Other pump controls HydroRanger 200 HMI 320 Operating Instructions 06 2018 A5E36281317 AC ...
Страница 352: ...Communications C 41 Single parameter access SPA HydroRanger 200 HMI 350 Operating Instructions 06 2018 A5E36281317 AC ...
Страница 354: ...Updating software HydroRanger 200 HMI 352 Operating Instructions 06 2018 A5E36281317 AC ...
Страница 359: ...HydroRanger 200 HMI Operating Instructions 06 2018 A5E36281317 AC 357 Conduit entry for Class I Div 2 applications F ...
Страница 360: ...Conduit entry for Class I Div 2 applications HydroRanger 200 HMI 358 Operating Instructions 06 2018 A5E36281317 AC ...
Страница 361: ...Conduit entry for Class I Div 2 applications HydroRanger 200 HMI Operating Instructions 06 2018 A5E36281317 AC 359 ...
Страница 362: ......
Страница 372: ...Programming chart G 1 Programming chart HydroRanger 200 HMI 370 Operating Instructions 06 2018 A5E36281317 AC ...
Страница 390: ...LCD menu structure H 1 LCD Menu Structure HydroRanger 200 HMI 388 Operating Instructions 06 2018 A5E36281317 AC ...
Страница 403: ......