Parameter reference
8.6 Setup (2.)
HydroRanger 200 HMI
Operating Instructions, 06/2018, A5E36281317-AC
199
Emptying indicator (2.8.1.10.)
Sets the empty rate required to activate the local display emptying indicator
Index
Single-point model
Dual-point model
Transducer
Level
Values
Range: 0.000 ... 99.00 m (or equivalent, depending on units)
Response rate (2.3.4.) (Page 174)
Related
•
Units (2.1.1.) (Page 162)
•
Span (2.2.2.) (Page 169)
•
Empty rate/minute (2.3.3.) (Page 173)
This value [in Units (2.1.1.) (Page 162) per minute] is automatically set to 1/10 of Empty
Rate/minute (2.3.3.) (Page 173).
Relay logic (2.8.1.11.)
Sets the logic applied to relays to determine the contact Open or Closed state.
Index
Relay
Options
Logic
Alarm contact
Pump or control contact
*Positive
Normally Closed
Normally Open
Negative
Normally Open
Normally Closed
Related
Relay function (2.8.1.4.) (Page 195)
The relay contact operation is Normally Closed for alarms and Normally Open for controls.
For more information, see Relay function (2.8.1.4.) (Page 195).
Note
This parameter is not reset by Master Reset (3.2.3.) (Page 254).
Power failure
When power is cut to the device, its relays fail to the following states:
Relay states
Relay
Fail State
1,2,4,5
Open
3,6
Open or Closed
1)
1)
Relays 3 and 6 are Form C types, so you can wire it either Normally Open or Normally Closed.
Check the wiring before programming.
To use Relays 3 or 6 as general alarm indicators, set Relay Logic (2.8.1.11.) to Negative and
wire the alarm for Normally Open operation. When an alarm event occurs (see below) or
when power is cut, the circuit closes and the alarm activates.
Содержание HydroRanger 200 HMI
Страница 2: ......
Страница 20: ...Introduction 1 5 Notes on warranty HydroRanger 200 HMI 18 Operating Instructions 06 2018 A5E36281317 AC ...
Страница 24: ...Safety notes HydroRanger 200 HMI 22 Operating Instructions 06 2018 A5E36281317 AC ...
Страница 28: ...Description 3 5 Modbus communication HydroRanger 200 HMI 26 Operating Instructions 06 2018 A5E36281317 AC ...
Страница 159: ...Parameter reference 8 2 Parameter indexing HydroRanger 200 HMI Operating Instructions 06 2018 A5E36281317 AC 157 ...
Страница 276: ...Parameter reference 8 10 Language 6 HydroRanger 200 HMI 274 Operating Instructions 06 2018 A5E36281317 AC ...
Страница 322: ...Pump control reference B 13 Other pump controls HydroRanger 200 HMI 320 Operating Instructions 06 2018 A5E36281317 AC ...
Страница 352: ...Communications C 41 Single parameter access SPA HydroRanger 200 HMI 350 Operating Instructions 06 2018 A5E36281317 AC ...
Страница 354: ...Updating software HydroRanger 200 HMI 352 Operating Instructions 06 2018 A5E36281317 AC ...
Страница 359: ...HydroRanger 200 HMI Operating Instructions 06 2018 A5E36281317 AC 357 Conduit entry for Class I Div 2 applications F ...
Страница 360: ...Conduit entry for Class I Div 2 applications HydroRanger 200 HMI 358 Operating Instructions 06 2018 A5E36281317 AC ...
Страница 361: ...Conduit entry for Class I Div 2 applications HydroRanger 200 HMI Operating Instructions 06 2018 A5E36281317 AC 359 ...
Страница 362: ......
Страница 372: ...Programming chart G 1 Programming chart HydroRanger 200 HMI 370 Operating Instructions 06 2018 A5E36281317 AC ...
Страница 390: ...LCD menu structure H 1 LCD Menu Structure HydroRanger 200 HMI 388 Operating Instructions 06 2018 A5E36281317 AC ...
Страница 403: ......