Parameter reference
8.6 Setup (2.)
HydroRanger 200 HMI
168
Operating Instructions, 06/2018, A5E36281317-AC
8.6.1.15
Scan time (2.1.15.)
Shows the elapsed time, in seconds, since the point displayed was last scanned.
Index
Level
Values
Range: 0.000 ... 9999 (Read only)
Related
Sensor mode (2.1.3.) (Page 163)
This may be viewed as an Auxiliary Reading in the RUN mode.
8.6.1.16
Shot delay (2.1.16.)
Adjusts the delay (in seconds) between transducer shots.
Index
Transducer
Values
Range: 0.1 ... 4.0
Preset: 0.5
Use this if transient acoustic noise within the vessel is causing measurement difficulties due
to echoes from one shot being received on the next. If more than one ultrasonic unit is
installed for redundancy, this value should be 0.
8.6.1.17
Shot/pulse mode (2.1.17.)
Determines what type of ultrasonic shots are fired.
Index
Single-point model
Dual-point model
Global
Transducer
Options
Short
*Short and long
Related
•
Empty (2.2.4.) (Page 170)
•
Long confidence (3.2.11.2.) (Page 262)
•
Long echo threshold (2.11.2.3.) (Page 223)
•
Short shot range (2.11.2.12.) (Page 226)
Increases the device's response when the monitored surface is close to the transducer face.
Select Short and long to have short and long acoustic shots fired for each measurement,
regardless of the transducer to surface distance. Select Short to have only short shots fired if
the Long confidence (3.2.11.2.) (Page 262) produced by a short shot exceeds the short Long
echo threshold (2.11.2.3.) (Page 223) and the monitored surface is always within the Short
shot range (2.11.2.12.) (Page 226).
Содержание HydroRanger 200 HMI
Страница 2: ......
Страница 20: ...Introduction 1 5 Notes on warranty HydroRanger 200 HMI 18 Operating Instructions 06 2018 A5E36281317 AC ...
Страница 24: ...Safety notes HydroRanger 200 HMI 22 Operating Instructions 06 2018 A5E36281317 AC ...
Страница 28: ...Description 3 5 Modbus communication HydroRanger 200 HMI 26 Operating Instructions 06 2018 A5E36281317 AC ...
Страница 159: ...Parameter reference 8 2 Parameter indexing HydroRanger 200 HMI Operating Instructions 06 2018 A5E36281317 AC 157 ...
Страница 276: ...Parameter reference 8 10 Language 6 HydroRanger 200 HMI 274 Operating Instructions 06 2018 A5E36281317 AC ...
Страница 322: ...Pump control reference B 13 Other pump controls HydroRanger 200 HMI 320 Operating Instructions 06 2018 A5E36281317 AC ...
Страница 352: ...Communications C 41 Single parameter access SPA HydroRanger 200 HMI 350 Operating Instructions 06 2018 A5E36281317 AC ...
Страница 354: ...Updating software HydroRanger 200 HMI 352 Operating Instructions 06 2018 A5E36281317 AC ...
Страница 359: ...HydroRanger 200 HMI Operating Instructions 06 2018 A5E36281317 AC 357 Conduit entry for Class I Div 2 applications F ...
Страница 360: ...Conduit entry for Class I Div 2 applications HydroRanger 200 HMI 358 Operating Instructions 06 2018 A5E36281317 AC ...
Страница 361: ...Conduit entry for Class I Div 2 applications HydroRanger 200 HMI Operating Instructions 06 2018 A5E36281317 AC 359 ...
Страница 362: ......
Страница 372: ...Programming chart G 1 Programming chart HydroRanger 200 HMI 370 Operating Instructions 06 2018 A5E36281317 AC ...
Страница 390: ...LCD menu structure H 1 LCD Menu Structure HydroRanger 200 HMI 388 Operating Instructions 06 2018 A5E36281317 AC ...
Страница 403: ......