![background image](http://html.mh-extra.com/html/siemens/d7-sys/d7-sys_manual_376751486.webp)
Closed-loop thyristor current control
5-46
System- and communication configuring D7-SYS - SIMADYN D
Edition 06.2002
PC6.
Significance
Value\connection
DIL
Pulse position tolerance [
°
]
Limit for the setpoint-actual value difference of the firing angle.
(Default: 1.0)
DIZ
Number of permissible continuous limit violations, DIL
(Default: 3)
ICC
Control word
(assignment, refer below)
SOL.QCC
→
PC6.ICC
DZ
Operation: Double firing
For DZ=1, a firing pulse pair of a phase is constantly output in
the constellation 1-4, 2-5, 3-6 or 4-1, 5-2, 6-3.
(Default: 0)
ACI
Handshake from the CAV block
CAV.ACO
→
PC6.ACI
TCP
Processing time of all FBs [ms]
(Default: 0 ms)
ACA
Processing time in [
°
]
(incl. 100
µ
s safety tolerance)
(Default: 0.0)
ZPA
Number of the firing pulse
PC6.ZPA
→
PA6.ZPA
(Default: 0)
ZZA
Diag.: Firing pulse adjustment number
(indicates the change of the number, only for changes > 60°.)
(Default: 0)
{-3...0...+4}
ZLA
Diag.: Status "Double firing state machine"
(Default: 0)
ZXA
Diag.: Status "Pulse position fault generation"
(Default: 0)
WAF
Firing angle setpoint
α
[
°
]
(max. changes/TA are limited by DAG or DAW.)
(Default: 0.0)
YEA
System deviation, firing angle controller
(Default: 0.0)
DZM
Operation: Double firing active
PC6.DZM
→
SOL.DZM
(Default: 0)
ZAH
Control word, hardware
(assignment, refer below)
(Default: 16#0000)
ACO
Handshake for EMF block
PC6.ACO
→
EMF.ACI
(Default: 0)
QSF
Fault word
PC6.QSF
→
SOL.QSP
(Default: 16#0000)
Fig. 5-25
I/O PC6