Communications configuring
3-34
System- and communication configuring D7-SYS - SIMADYN D
Edition 12.2003
3.4.1.2
Central coupling block @CSH11
A @CSH11 function block must be configured to initialize the CSH11.
Input MAA is a SINEC H1 input.
The station address for the CSH11 is specified at this initialization input.
The name comprises of precisely 12 characters. All hexadecimal
characters are permitted.
Example: '080006010001'
Alarms and faults/errors are displayed at the ECL outputs (error class)
and ECO (error code) of the central coupling block.
ECL ECO
Explanation
0 (alarm)
0
o.k.
1
Station address erroneous
2
Station address does not match the
database
5
Coupling type incorrect
6
No database or database incomplete
7
CSH11 in the STOP condition
> 0 (error)
Any
Irreparable error; red LED flashes.
Note the error class and -code and contact
Siemens AG.
Table 3-18
Information at the outputs ECL and ECO
NOTE
If ECO = 6 and simultaneously the green LED on the CSH11 is lit (the
database is consistent), then the NML software should be corrected as
follows:
•
"CSH1 SINEC TF00" must be selected under the NML menu item
import FVT
("System FVT00" is not required).
Under the NML menu item
application associations > FVT
assignment
, the available (standard) application associations
must be
assigned to FVT "CSH1 SINEC TF00".
3.4.2
Communications via SINEC H1 layer 2
NOTE
An NML configuring tool is not required when using layer 2!
When establishing communications via SINEC H1 layer 2, the address
connections AT and AR are configured as follows.
Initialization
Information at
input MAA
Information at
outputs ECL and
ECO
General