Closed-loop thyristor current control
5-78
System- and communication configuring D7-SYS - SIMADYN D
Edition 06.2002
Connec-
tion
Significance
Value
Value
change
Type
SOL.TH0
Thyristor hold-off time [ms]
Condition: 0.5 ms
≤
TH0
≤
131 ms, > YW2\bit10 =1
10 ms
Init
SOL.TCP
Thyristor pulse suppression time [ms]
Condition: 0.0 ms
≤
TH0
≤
20000 ms ,
> YW2\bit10 =1
20 ms
Init
SOL.TCD
Monitoring time for torque change M1
⇔
M2
1000 ms
SOL.IPL
Pulse inhibit = 1 effective immediately !
0
SOL.UNM
Mode: Handling the undervoltage (Sitor)
2
SOL.ION
On command, closed-loop thyristor current control
0
SOL.IOF
Off command, closed-loop thyristor current control
0
SOL.ON1
Enable, only torque direction M1
0
SOL.OF1
Off command, torque direction M1
0
SOL.ON2
Enable, only torque direction M2
0
SOL.OF2
Off command, torque direction M2
0
SOL.IEF
Mode: Use calculated EMF value
(FB EMF available )
1
SOL.NZM
Zero current signal from the SITOR set Y/N=0/1
0
SOL.WC1
Current setpoint 1
(or connection)
0.0
SOL.WC2
Current setpoint 2
(or connection)
0.0
SOL.WCL
Switch-on threshold for torque direction (abs. value)
0.01
SOL.TM0
Monitoring time for torque direction M0
2000ms
SOL.IF1
Fault, external 1
0
SOL.IF2
Fault, external 2
0
SOL.HMH
Enables bits for the hardware signaling word YHW
16#FFFF
SOL.HM1
Enables bits for the fault word YF1
16#FFFF
SOL.HM2
Enables bits for the fault word YF2
16#FFFF
SOL.HP1
Enables bits from YF1 for immediate pulse inhibit
16#0000
SOL.HP2
Enables bits from YF2 for immediate pulse inhibit
16#0000
SOL.MNE
Group inhibit, fault word YF1 and YHW
16#067E
Connec-
tion
Significance
Value
Value
change
Type
CSP.WCU
Positive current limit
(absolute value)
1.0
CSP.WCL
Negative current limit
(absolute value)
1.0
CSP.GLI
Gradient for setpoint smoothing
0.6
CSP.IL
Gradient for integrator inhibit
0.6