Communications
configuring
System- and communication configuring D7-SYS - SIMADYN D
3-313
Edition 12.2003
•
Connection name: Max 3 characters, the first character must be a
letter
•
$ signal name: Max 6 characters, the first character must be a letter
•
Scaling range: 0.00001 -- 99999
3.29.6 NML
configuring
software for CSH11
The configuring tool NML is required to configure the bus for the CSH11
coupling module (with integrated CP1470).
The handling of the NML configuring tool will not be discussed here but if
you require further information refer to the NML-CP Manual.
The following configuring software is suitable for establishing a
connection between WinCC and SIMADYN D via a CSH11 module using
the SINEC H1 protocol (Industrial Ethernet level 4).
Siemens AG SINEC NML V 3.01 Documentation communications
19.02.1998
•
Node type: CP 147x
•
Node name: roland
•
Page: 1 / 1
•
Interface type: CP 147x
•
Interface name: CP 147x
•
Interface profile: CSH11_E4_2000
•
Bus address: 080006010002 (SIMADYN D)
•
Transport connection.: 6
•
Application designation.: 26
•
Data basis length: 5888 bytes
•
No. of FVTs: 1
1. Transport connection
SDCOR1
•
Local TSAP-ID: AG_WINCC
•
Remote TSAP-ID: WINCC_AG
•
Remote bus address: 080006010001 (PC)
Configuring
software example
Basic node data
Communication
relationships