Communications configuring
3-248
System- and communication configuring D7-SYS - SIMADYN D
Edition 12.2003
•
Input STC connection is not listed here. For STC = 1, the length
specification for the message text always corresponds with the
maximum length; for STC = 0, it corresponds to the actual message
text length.
SNV=TRUE (message numbers available)
STM=TRUE (message text available)
SSF=TRUE (standardized format)
Contents Message
structure
(max. 108 bytes)
Net data structure
Data format
No. of data
Spontaneous ID
Unsigned8
1. variable unit
Unsigned8
2
Sequence number
Unsigned8
Message type descrip.
1 Octet
2. variable unit
Octet-String
2
Message type
1 Octet
Prefix
Floating-Point
3. variable unit
Floating-Point
3
Suffix Floating-Point
Measured value
Floating-Point
Measured value
dimensions text
8 characters
4. variable unit
Visible-String
92
Message instant
24 characters
Message text
max. 60 characters
Table 3-75
Standard format with number and text
SNV=FALSE (message numbers not available)
STM=TRUE (message text available)
SSF=TRUE (standardized format)
Contents Message
structure
(max. 100 bytes)
Net data structure
Data format
No. of data
Spontaneous ID
Unsigned8
1. variable unit
Unsigned8
2
Sequence number
Unsigned8
Message type descrip.
1 Octet
2. variable unit
Octet-String
2
Message type
1 Octet
Measured value
Floating-Point
3. variable unit
Floating-Point
1
Measured value
dimensions text
8 characters
4. variable unit
Visible-String
92
Message instant
24 characters
Message text
max. 60 characters
Table 3-76
Standard format without number with text