APPENDIX
A-
IMR01N12-E7
26
Triac output
Output method:
AC output (Zero-cross method)
Allowable load current:
0.4 A (Ambient temperature 40
C or less)
Ambient temperature 50
C: 0.3 A
Load voltage:
75 to 250 V AC
Minimum load current:
30 mA
ON voltage:
1.6 V or less (at maximum load current)
OUT4, OUT5 (Used for event output)
Number of outputs:
Up to 2 points (Specify when ordering)
If OUT3 is selected for the Sensor power supply (optional), OUT4 and OUT5 cannot be used.
Output type:
Relay contact output
Contact type:
1a contact
Rating:
250 V AC, 1A (Resistive load)
Electrical life:
300,000 or more (Rated load)
Transmission output
Number of outputs:
Up to 3 points (Varies depending on the Output logic selection setting and Output type)
Output contents:
Measured value, Set value, Manipulated output value and Deviation
Scaling range:
Measured value/Set value:
Same as input range
Manipulated
output
value:
50 to
105.0
Deviation:
Input span
Performance
Display accuracy
(At the ambient temperature 23
C ±2
C)
:
Pressure sensor input
(
Strain gauge type pressure sensor
)
0.1 % of span
0.5 % of span (When combined with pressure sensor)
TC input (K, J, T, PL II, E)
Less
than
100
C [
148
F]:
1.0
C [
2.0
F]
Less
than
100 to
500
C [
148 to
932
F]:
0.5
C [
1.0
F]
500
C [932
F] or more:
(0.1 % of reading
1digit)
TC input (S, R, N, W5Re, W26Re)
Less
than
100
C [
148
F]:
2.0
C [
4
F]
Less
than
100
C to
1000
C [
148 to
1832
F]:
1.0
C [
2.0
F]
1000
C [1832
F] or more:
(0.1 % of reading
1digit)
TC input (B)
Less than 400
C [752
F]:
70.0
C [
130
F]
Less
than
400
C to 1000
C [752 to 1832
F]:
1.0
C [
2.0
F]
1000
C [1832
F] or more:
(0.1 % of reading
1digit)
RTD input
Less
than
200
C [392
F]:
0.2
C [
0.4
F]
200
C [392
F] or more:
(0.1 % of reading
1digit)
Voltage input
0.1 % of span
Current input
0.1 % of span
Cold-junction temperature compensation error:
1.0
C (At the ambient temperature 23
C ±2
C)
1.5
C (At the ambient temperature
10 to
50
C)
Minimum indication resolution:
Pressure sensor input:
Rated pressure:
Less than 1 MPa:
0.0001 MPa
Less than 10 MPa: 0.001 MPa
Less than 100 MPa: 0.01 MPa
100 MPa or more:
0.1 MPa
TC input:
0.1
C [
F]
(The decimal point position of the input range is selectable.)
RTD input:
0.01
C [
F]
(The decimal point position of the input range is selectable.)
Voltage/Current input:
1 to 0.0001 (Programmable)