1.
OUTLINE
IMR01N12-E7
5
OUTPUT
Up to five outputs are available. They may be used as Control output, Event output or
Transmission output by specifying the output type or by activating the output logic
function (output logic selection).
Output1 to 3 (OUT1 to OUT3):
Control output, Event output, or Transmission output can be allocated to output 1 to 3.
(Refer to P. 76 to 84.)
Number of outputs and output types must be specified when ordering.
Output types available for OUT1 to OUT3 are shown in the table below.
Relay contact output
250 V AC, 3A (Resistive load), 1a contact
Voltage pulse output
0/12 V DC (Load resistance: 600
or more)
Triac output
0.4 A (Allowable load current)
Voltage output
0 to 5 V DC, 1 to 5 V DC, 0 to 10 V DC (Load resistance: 1 k
or more)
Current output
0 to 20 mA DC, 4 to 20 mA DC (Load resistance: 600
or less)
OUT3 is isolated from both OUT1 and OUT2.
OUT1 and OUT2 are not isolated from each other except for relay or triac output.
When relay or triac output is used, there is isolation between outputs.
There is isolation between input and output.
There is isolation between output and power supply terminals.
OUT3 can be selected for Sensor power supply. (Specify when ordering)
Output 4 to 5 (OUT4 to OUT5):
The output type for OUT4 and OUT5 is relay only. OUT4 and OUT5 can be used for
Allowable load vent output. (Refer to P. 76 to 84.)
Relay contact output
250 V AC, 1A (Resistive load), 1a contact
If the sensor power supply is selected for OUT3, OUT4 and OUT5 cannot be used.
Event output function (EV1 to EV4)
The following event types can be selected for EV1 to EV4.
Deviation high
Band
SV high
Deviation low
Process high
SV low
Deviation high/low
Process low
LBA (Only EV3 and EV4 can be selected)
The maximum number of Event output is four.
Output allocation is necessary to output the event state from output terminals.
(Refer to P. 76.)
Transmission output 1 to 3 (AO1 to AO3):
Maximum three transmission output can be allocated to OUT1, OUT2, and OUT3.
Maximum number of output available for transmission output varies by other output use
for control output and event output. Parameter values shown in the following table can be
output by transmission output. (Refer to P. 79.)
Input 1 side
Measured value (PV), Set value (SV), Manipulated output value (MV),
Deviation (PV
SV)
Input 2 side
Measured value (PV), Set value (SV), Manipulated output value (MV),
Deviation (PV
SV)