APPENDIX
A-10
IMR01N12-E7
Function block F22: Input 2
Name Parameter Data
range
Factory set
value
User set
value
Page
Input 2_input type selection
(2. InP)
TC input
0: K
200 to
1372
C
328.0 to
2501.6
F
1: J
200 to
1200
C
328.0 to
2192.0
F
2: R
50 to
1768
C
58.0 to
3214.4
F
3: S
50 to
1768
C
58.0 to
3214.4
F
4:
B
0 to 1800
C
32.0 to 3272.0
F
5: E
200 to
1000
C
328.0 to
1832.0
F
6:
N
0 to 1300
C
32.0 to 2372.0
F
7: T
200 to
400
C
328.0 to
752.0
F
8: W5Re/W26Re
0 to 2300
C
32.0 to 4172.0
F
9:
PLII
0 to 1390
C
32.0 to 2534.0
F
RTD input (3-wire system)
12: Pt100
200 to
850
C
328.0 to
1562.0
F
13: JPt100
200 to
600
C
328.0 to
1112.0
F
Voltage (V)/Current (I) inputs
19999 to
99999
14: 0 to 20 mA DC 24:
±
100 mV DC
15: 4 to 20 mA DC 25:
±
10 mV DC
16: 0 to 10 V DC
26:
±
10 V DC
17: 0 to 5 V DC
27:
±
5 V DC
18: 1 to 5 V DC
28:
±
1 V DC
19: 0 to 1 V DC
20: 0 to 100 mV DC
21: 0 to 10 mV DC
22, 23: Unused (Not available)
Based on
model code.
When not
specifying:
Type K
P.
66
Input 2_display unit selection
(2.UnIT)
0:
C
1:
F
The display unit selection becomes
invalidated when the Voltage (V)/
Current (I) input is selected as input
type.
0
P.
67
Continued on the next page.