APPENDIX
A-
IMR01N12-E7
6
Continued from the previous page.
Name Parameter Data
range
Factory set
value
User set
value
Page
Input 1_control response
parameter
(1. rPt)
0: Slow
1: Medium
2: Fast
0
P.
38
Input 2_ proportional band
(2. P)
TC/RTD inputs:
0 (0.0, 0.00) to Input span
(Unit:
C [
F])
(Varies with the setting of the
Decimal point position)
Voltage (V)/Current (I) inputs:
0.0 to 1000.0 % of input span
0 (0.0, 0.00): ON/OFF action
30.0
P.
37
Input 2_integral time
(2. I)
OFF (PD action)
1 to 3600 seconds,
0.1 to 3600.0 seconds, or
0.01 to 360.00 seconds
(Varies with the setting of the
Integral/Derivative time decimal
point position selection)
240.00
P.
37
Input 2_derivative time
(2. d)
OFF (PI action)
1 to 3600 seconds,
0.1 to 3600.0 seconds, or
0.01 to 360.00 seconds
(Varies with the setting of the
Integral/Derivative time decimal
point position selection)
60.00
P.
37
Input 2_control response
parameter
(2. rPt)
0: Slow
1: Medium
2: Fast
0
P.
38
Input 1_setting change rate
limiter (up)
(1.SVrU)
OFF (Unused)
0.1 to Input span/unit time *
OFF
P.
38
Input 1_setting change rate
limiter (down)
(1.SVrd)
(Varies with the setting of the
Decimal point position)
OFF
P.
39
Input 2_setting change rate
limiter (up)
(2. SVrU)
OFF
P.
38
Input 2_setting change rate
limiter (down)
(2.SVrd)
* Unit time: 60 seconds (factory set
value)
OFF
P.
39
Area soak time
(AST)
0 minute 00.00 second to
9 minutes 59.99 seconds or
0 hour 00 minute 00 second to
9 hours 59 minutes 59 seconds
0.00.00
P.
40
Link area number
(LnKA)
OFF (No link)
1 to 16
OFF
P.
41