APPENDIX
IMR01N12-E7
A-
5
A-3. Parameter setting mode
Name Parameter Data
range
Factory set
value
User set
value
Page
Event 1 set value
(EV1)
Deviation:
Input span to
Input span
Process/SV:
Input scale low to Input scale high
50.0
P.
35
Event 2 set value
(EV2)
Deviation:
Input span to
Input span
Process/SV:
Input scale low to Input scale high
50.0
P.
35
Event 3 set value
(EV3)
Deviation:
Input span to
Input span
Process/SV:
Input scale low to Input scale high
50.0
P.
35
Control loop break alarm 1
(LBA1) time
(LbA1)
OFF (Unused)
1 to 7200 seconds
480
P.
35
LBA1 deadband
(Lbd1)
0.0 to Input span
(Varies with the setting of the
Decimal point position)
0.0
P.
36
Event 4 set value
(EV4)
Deviation:
Input span to
Input span
Process/SV:
Input scale low to Input scale high
50.0
P.
35
Control loop break alarm 2
(LBA2) time
(LbA2)
OFF (Unused)
1 to 7200 seconds
480
P.
35
LBA2 deadband
(Lbd2)
0.0 to Input span
(Varies with the setting of the
Decimal point position)
0.0
P.
36
Input 1_ proportional band
(1. P)
0.0 to 1000.0 % of input span
0.0: ON/OFF action
100.0
P.
37
Input 1_integral time
(1. I)
OFF (PD action)
1 to 3600 seconds,
0.1 to 3600.0 seconds, or
0.01 to 360.00 seconds
(Varies with the setting of the
Integral/Derivative time decimal
point position selection)
5.00
P.
37
Input 1_derivative time
(1. d)
OFF (PI action)
1 to 3600 seconds,
0.1 to 3600.0 seconds, or
0.01 to 360.00 seconds
(Varies with the setting of the
Integral/Derivative time decimal
point position selection)
OFF
P.
37
Continued on the next page.