APPENDIX
IMR01N12-E7
A-
25
Event input (Optional)
Number of inputs:
Up to 5 points
Input method:
Dry contact input
OPEN (OFF) state: 500 k
or more
CLOSE (ON) state: 10
or less
Functions:
Memory area selection, RUN/STOP transfer, Remote/Local transfer,
Auto/Manual transfer, Hold reset, Interlock release,
Manual output up/down (Motor RPM up/down),
Manual output 0 % reset (Motor RPM reset)
Control action
Number of control points
:
Up to 2 points
Control method:
Brilliant PID control
Direct action or Reverse action is available
With Autotuning, Output limiter and Output change rate limiter
Control loop break alarm (LBA)
LBA time:
0 to 7200 seconds (0: OFF)
LBA deadband:
0 to Input span
Output
Sensor power supply (Optional)
Rated voltage:
24 V DC
5 %
Rated current:
24 mA max.
Sensor power supply is isolated from both OUT1 and OUT2
OUT3 to OUT5: Not available
Power supply for strain gauge type of pressure sensor
Rated voltage:
8 V DC
3 %
Temperature drift:
80 ppm/
C
Rated current:
30 mA max.
OUT1 to OUT3 (Used for control output, event output or transmission output)
Number of outputs:
Up to 3 points (Specify when ordering)
OUT3 is isolated from both OUT1 and OUT2.
OUT1 and OUT2 are not isolated from each other except for relay or triac output.
When relay or triac output is used, there is isolation between outputs.
There is isolation between input and output.
There is isolation between output and power supply terminals.
If the Sensor power supply (optional) is specified, OUT3 cannot be used.
Output type:
Relay contact output
Contact type:
1a contact
Rating:
250 V AC, 3A (Resistive load)
Electrical life:
300,000 or more (Rated load)
Voltage pulse output
Output voltage:
0/12 V DC
Allowable load resistance: 600
or more
Current output
Output current:
0 to 20 mA DC, 4 to 20 mA DC (Specify when ordering)
Allowable load resistance: 600
or less
Voltage output
Output type:
0 to 5 V DC, 1 to 5 V DC, 0 to 10 V DC
(Specify
when
ordering)
Allowable load resistance: 1 k
or more