8. ENGINEERING MODE
IMR01N12-E7
80
8.10 Event 1 (F41) Event 3 (F43)
Event 2 (F42) Event 4 (F44)
Event type selection (ES1, ES2, ES3, ES4)
Use to select a type of the event 1, 2, 3 and 4.
Data range:
0:
None
5:
Process
high
1
1: Deviation high
1
6: Process low
1
2: Deviation low
1
7: SV high
3: Deviation high/low
1
8: SV low
4: Band
1
9: Control loop break alarm (LBA)
2
1
Event hold action is available.
2
“9: Control loop break alarm (LBA)” can be selected only for Event 3 and Event 4.
Factory set value:
0
Related parameters:
Output logic selection (P. 76), Output timer setting (P. 77),
Alarm lamp lighting condition setting (P. 77), Event hold action (P. 82),
Event differential gap (P. 83), Event assignment (P. 84),
Event action at input error (P. 84), Event set value (P. 35),
Control loop break alarm (LBA) time (P. 35), LBA deadband (P. 36)
Event action type
Continued on the next page.
*
(Event set value is greater than 0.)
*
(Event set value is greater than 0.)
Deviation high:
Deviation low:
Deviation high/low:
Band:
Process high:
*
(Event set value is less than 0.)
*
(Event set value is less than 0.)
Process low:
SV high:
SV low:
OFF
ON
PV
Low
High
☆
OFF
ON
Low High
PV
☆
( : Set value (SV) : Event set value
☆
: Event differential gap)
ON OFF
PV
Low High
☆
ON OFF
PV
Low
High
☆
OFF
ON OFF
PV
Low
High
☆
☆
ON OFF ON
PV
Low High
☆
☆
ON OFF
PV
Low
High
☆
OFF
ON
PV
Low High
☆
ON OFF
MV
Low
High
☆
OFF
ON
MV
Low High
☆