4.
SETTING
IMR01N12-E7
25
Input type and input range display
This instrument immediately confirms inputs type symbol and input range following power ON.
Example: When sensor type of Input 1 is pressure input, and sensor type of Input 2 is K thermocouple
(2-input controller)
Symbol
Input type
Input range
K
200.0 to
1372.0
C,
328.0 to
2501.6
F
J
200.0 to
1200.0
C,
328.0 to
2192.0
F
T
200.0 to
400.0
C,
328.0 to
752.0
F
S
50.0 to
1768.0
C,
58.0 to
3214.4
F
R
50.0 to
1768.0
C,
58.0 to
3214.4
F
PLII
0.0 to 1390.0
C,
32.0 to 2534.0
F
N
0.0 to 1300.0
C,
32.0 to 2372.0
F
W5Re/W26Re
0.0 to 2300.0
C,
32.0 to 4172.0
F
E
200.0 to
1000.0
C,
328.0 to
1832.0
F
B
0.0 to 1800.0
C,
32.0 to 3272.0
F
Pt100
(3-wire system)
200.0 to
850.0
C,
328.0 to
1562.0
F
JPt100
(3-wire system)
200.0 to
600.0
C,
328.0 to
1112.0
F
Voltage
(mV, V)
Programmable range
Current
(mA)
(
19999 to
99999)
Pressure
(MPa)
0.0 to 250.0 MPa
After the input type symbol and the input range are displayed on the display
unit, the PV1/SV1 monitor screen (SV setting & Monitor mode) is
displayed.
These displays
are not displayed
for the 1-input
controller.
Symbol
Unit for input and SV display (MP: MPa, br: bar, kg: kgf/cm
2
, PS: psi)
Pressure sensor type symbol
(ST: Strain gauge type of pressure sensor) *
Pressuer input range high *
(Input scale high: 50.0)
Pressuer input range low *
(Input scale low: 0.0)
* Input Type Symbol Table
Input range high *
Input range low *
Unit for input and SV display
(Celsius:
C, Fahrenheit:
F,
Voltage/Current input: no
character shown)
Input type symbol *
PV1
Power ON
Input 1
Input 2
SV setting &
Monitor mode
(PV1/SV1 monitor)
Automatically (in 1 sec)
[1-input controller: in 2 sec]
PV1
PV2
Automatically
(in 1 sec)
Automatically (in 1 sec)
[1-input controller: in 2 sec]
Automatically
(in 1 sec)
PV2
AREA
PV1
MAN