8. ENGINEERING MODE
IMR01N12-E7
90
Manipulated output value at input error (1. PSM, 2. PSM)
When the measured value reaches Input error determination point and Action at input error is set to “1”, this
manipulated value is output.
Data range:
5.0 to
105.0 %
Factory set value:
Input 1_manipulated output value at input error (1. PSM):
5.0
Input 2_manipulated output value at input error (2. PSM):
5.0
Related parameters:
Input error determination point (high) (P. 70), Input error determination point (low) (P. 71),
Action at input error (high) (P. 89), Action at input error (low) (P. 89)
Manipulated output value when transferred to Auto from Manual
(1. PSM’, 2. PSM’)
This is the final Manipulated output value used under Manual control when the control mode is transferred to
Auto control from Manual control.
Data range:
5.0 to
105.0 %
Factory set value:
Related parameters:
MV transfer function (P. 92)
This manipulated output value is used as a manipulated output value under Manual control when
transferred to Manual control from Auto control for event input with “MV transfer function: 1 (Used)”
selected.
Output change rate limiter (up) (1. orU, 2. orU)
Use to set the Output change rate limiter (up) to limit of the variation of output is set.
Data range:
0.0 to 1000.0 %/second of manipulated output
0.0: Unused
Factory set value:
Input 1_output change rate limiter (up) (1. orU): 0.0
Input 2_output change rate limiter (up) (2. orU): 0.0
Related parameters:
Output change rate limiter (down) (P. 91), Output limiter high (P. 92),
Output limiter low (P. 92)
Output Change Rate Limiter:
The Output change rate limiter limits the variation of Manipulated output (MV) per
second. This function is suitable for an application in which a sudden MV change is not
acceptable.
Continued on the next page.